1926.961(c) Deenergizing Lines and Equipment
Go To Full Code Chapter
1926.961(c)(1) Request to Deenergize
The employee that the employer designates pursuant to paragraph (b) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (c) of this section) and is responsible for the clearance.
1926.961(c)(2) Open Disconnecting Means
The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.
1926.961(c)(3) Automatically and Remotely Controlled Switches
The employer shall ensure that automatically and remotely controlled switches that could cause the opened disconnecting means to close are also tagged at the points of control. The employer shall render the automatic or remote control feature inoperable, unless its design does not so permit.
1926.961(c)(4) Network Protectors
The employer need not use the tags mentioned in paragraphs (c)(2) and (c)(3) of this section on a network protector for work on the primary feeder for the network protector's associated network transformer when the employer can demonstrate all of the following conditions:
1926.961(c)(4)(i)
Every network protector is maintained so that it will immediately trip open if closed when a primary conductor is deenergized;
1926.961(c)(4)(ii)
Employees cannot manually place any network protector in a closed position without the use of tools, and any manual override position is blocked, locked, or otherwise disabled; and
1926.961(c)(4)(iii)
The employer has procedures for manually overriding any network protector that incorporate provisions for determining, before anyone places a network protector in a closed position, that: The line connected to the network protector is not deenergized for the protection of any employee working on the line; and (if the line connected to the network protector is not deenergized for the protection of any employee working on the line) the primary conductors for the network protector are energized.
1926.961(c)(5) Tags
Tags shall prohibit operation of the disconnecting means and shall indicate that employees are at work.
1926.961(c)(6) Test for Energized Condition
After the applicable requirements in paragraphs (c)(1) through (c)(5) of this section have been followed and the system operator gives a clearance to the employee in charge, the employer shall ensure that the lines and equipment are deenergized by testing the lines and equipment to be worked with a device designed to detect voltage.
1926.961(c)(7) Install Grounds
The employer shall ensure the installation of protective grounds as required by § 1926.962.
1926.961(c)(8) Consider Lines and Equipment Deenergized
After the applicable requirements of paragraphs (c)(1) through (c)(7) of this section have been followed, the lines and equipment involved may be considered deenergized.
1926.961(c)(9) Transferring Clearances
To transfer the clearance, the employee in charge (or the employee's supervisor if the employee in charge must leave the worksite due to illness or other emergency) shall inform the system operator and employees in the crew; and the new employee in charge shall be responsible for the clearance.
1926.961(c)(10) Releasing Clearances
To release a clearance, the employee in charge shall:
1926.961(c)(10)(i)
Notify each employee under that clearance of the pending release of the clearance;
1926.961(c)(10)(ii)
Ensure that all employees under that clearance are clear of the lines and equipment;
1926.961(c)(10)(iii)
Ensure that all protective grounds protecting employees under that clearance have been removed; and
1926.961(c)(10)(iv)
Report this information to the system operator and then release the clearance.
1926.961(c)(11) Person Releasing Clearance
Only the employee in charge who requested the clearance may release the clearance, unless the employer transfers responsibility under paragraph (c)(9) of this section.
1926.961(c)(12) Removal of Tags
No one may remove tags without the release of the associated clearance as specified under paragraphs (c)(10) and (c)(11) of this section.
1926.961(c)(13) Reenergizing Lines and Equipment
The employer shall ensure that no one initiates action to reenergize the lines or equipment at a point of disconnection until all protective grounds have been removed, all crews working on the lines or equipment release their clearances, all employees are clear of the lines and equipment, and all protective tags are removed from that point of disconnection.
[79 FR 20708-20709, July 10, 2014]
[79 FR 20708-20709, July 10, 2014]
Upcodes Diagrams
Related Code Sections
1926.961(c) Electric Power Transmission and Distribution, Deenergizing Lines and Equipment
of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used ...
1926.961(c)(11) Electric Power Transmission and Distribution, Person Releasing Clearance
Only the employee in charge who requested the clearance may release the clearance, unless the employer transfers responsibility under paragraph (c)(9 ...
1926.961(c)(12) Electric Power Transmission and Distribution, Removal of Tags
No one may remove tags without the release of the associated clearance as specified under paragraphs (c)(10) and (c)(11) of this section ...
1926.961(c)(2) Electric Power Transmission and Distribution, Open Disconnecting Means
be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so ...
1926.961(c)(3) Electric Power Transmission and Distribution, Automatically and Remotely Controlled Switches
The employer shall ensure that automatically and remotely controlled switches that could cause the opened disconnecting means to close are also tagged ...