Deck beams shall be attached to deck posts in accordance with Figure R507.7.1 or by other equivalent means capable to resist lateral displacement. Manufactured post-to-beam connectors shall be sized for the post and beam sizes. All bolts shall have washers under the head and nut.
Exception: Where deck beams bear directly on footings in accordance with Section R507.8.1.
FIGURE R507.7.1 DECK BEAM TO DECK POST
Exception: Where deck beams bear directly on footings in accordance with Section R507.8.1.
For SI: 1 inch = 25.4 mm.
FIGURE R507.7.1 DECK BEAM TO DECK POST