3307.6.4.5 Deck
JUMP TO FULL CODE CHAPTER
The deck of the sidewalk shed shall consist of 2-inch (51 mm) thick wood plank or equivalent material and shall be capable of sustaining the loads required by Section 3307.6.4.2. The deck shall be solid, or shall consist of planking laid close and made tight. Where the edge of the sidewalk shed abuts a building or structure, the decking shall be brought tight to the face of the building or structure.
Exception: Where it is not possible to bring the deck tightly against the face of the building or structure, the deck shall be brought to within 1 inch (25 mm) of the face of the building or structure, with the resulting gap sealed or covered by material of sufficient manner and strength capable of trapping falling debris.
Exception: Where it is not possible to bring the deck tightly against the face of the building or structure, the deck shall be brought to within 1 inch (25 mm) of the face of the building or structure, with the resulting gap sealed or covered by material of sufficient manner and strength capable of trapping falling debris.
Related Code Sections
1604.8.3 Structural Design, Decks
Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical ...
NYC Building Code 2008 > 16 Structural Design > 1604 General Design Requirements > 1604.8 Anchorage > 1604.8.3 Decks
1604.8.3 Structural Design, Decks
Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical ...
NYC Building Code 2014 > 16 Structural Design > 1604 General Design Requirements > 1604.8 Anchorage > 1604.8.3 Decks
3307.6.4.5 Safeguards During Construction or Demolition, Deck
The deck of the sidewalk shed shall consist of 2-inch (51 mm) thick wood plank or equivalent material and shall be capable of sustaining the loads ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3307 Protection of Pedestrians > 3307.6 Sidewalk Sheds > 3307.6.4 Design and Construction of Sidewalk Sheds > 3307.6.4.5 Deck
1105.2 Storm Drainage, Flat Decks
Roof drain strainers for use on sun decks, parking decks and similar areas that are normally serviced and maintained shall comply with Section 1105.1 ...
1105.2 Storm Drainage, Flat Decks
Roof drain strainers for use on sun decks, parking decks and similar areas that are normally serviced and maintained shall comply with Section 1105.1 ...