// CODE SNIPPET
18.2.5.2 Dead-End Corridors
JUMP TO FULL CODE CHAPTER
Dead-end corridors shall not exceed 30 ft (9.1 m).
Related Code Sections
1105.6.5 Construction Requirements for Existing Buildings, Dead-End Corridors
In smoke compartments containing patient sleeping rooms and treatment rooms, dead-end corridors shall not exceed 30 feet (9144 mm) unless approved ...
Fire Code 2018 of Kansas > 11 Construction Requirements for Existing Buildings > 1105 Construction Requirements for Existing Group I-2 > 1105.6 Means of Egress > 1105.6.5 Dead-End Corridors
18.2.5.2 New Health Care Occupancies, Dead-End Corridors
Dead-end corridors shall not exceed 30 ft (9.1 m) ...
Life Safety Code 2018 of Kansas > 18 New Health Care Occupancies > 18.2 Means of Egress Requirements > 18.2.5 Arrangement of Means of Egress > 18.2.5.2 Dead-End Corridors
19.2.5.2* Existing Health Care Occupancies, Dead-End Corridors
Existing dead-end corridors not exceeding 30 ft (9.1 m) shall be permitted. Existing dead-end corridors exceeding 30 ft (9.1 m) shall be permitted ...
Life Safety Code 2018 of Kansas > 19 Existing Health Care Occupancies > 19.2 Means of Egress Requirements > 19.2.5 Arrangement of Means of Egress > 19.2.5.2* Dead-End Corridors
805.6 Alterations—Level 2, Dead-End Corridors
Dead-end corridors in any work area shall not exceed 35 feet (10 670 mm). Exceptions: Where dead-end corridors of greater length ...
Existing Building Code 2018 of Kansas > 8 Alterations—Level 2 > 805 Means of Egress > 805.6 Dead-End Corridors
1020.4 Means of Egress, Dead Ends
Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead-end corridors do not exceed 20 ...