1029.9.5 Dead-End Aisles
JUMP TO FULL CODE CHAPTER
Each end of an aisle shall be continuous to a cross aisle, foyer, doorway, vomitory, concourse or stairway in accordance with Section 1029.9.7 having access to an exit.
Exceptions:
- Dead-end aisles shall be not greater than 20 feet (6096 mm) in length.
- Dead-end aisles longer than 16 rows are permitted where seats beyond the 16th row dead-end aisle are not more than 24 seats from another aisle, measured along a row of seats having a minimum clear width of 12 inches (305 mm) plus 0.6 inch (15.2 mm) for each additional seat above seven in the row where seats have backrests or beyond 10 where seats are without backrests in the row.
- For smoke-protected or open-air assembly seating, the dead-end aisle length of vertical aisles shall not exceed a distance of 21 rows.
- For smoke-protected or open-air assembly seating, a longer dead-end aisle is permitted where seats beyond the 21-row dead-end aisle are not more than 40 seats from another aisle, measured along a row of seats having an aisle accessway with a minimum clear width of 12 inches (305 mm) plus 0.3 inch (7.6 mm) for each additional seat above seven in the row where seats have backrests or beyond 10 where seats are without backrests in the row.
Related Code Sections
1029.9.5 Means of Egress, Dead-End Aisles
having access to an exit. Exceptions: Dead-end aisles shall be not greater than 20 feet (6096 mm) in length. Dead-end aisles longer than 16 ...
Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly > 1029.9 Assembly Aisles Are Required > 1029.9.5 Dead-End Aisles
1030.9.5 Means of Egress, Dead-End Aisles
having access to an exit . Exceptions: Dead-end aisles shall be not greater than 20 feet (6096 mm) in length. Dead-end aisles longer than ...
Building Code 2021 of Illinois > 10 Means of Egress > 1030 Assembly > 1030.9 Assembly Aisles Are Required > 1030.9.5 Dead-End Aisles
1020.4 Means of Egress, Dead Ends
Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead-end corridors do not exceed 20 ...
1020.5 Means of Egress, Dead Ends
Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead-end corridors do not exceed 20 ...
1301.6.12 Performance Compliance Methods, Dead Ends
into Table 1301.7 under Safety Parameter 1301.6.12, Dead Ends, for means of egress and general safety. TABLE 1301.6.12 DEAD-END VALUES ...
Existing Building Code 2018 of Illinois > 13 Performance Compliance Methods > 1301 General > 1301.6 Evaluation Process > 1301.6.12 Dead Ends