6.4.3.1.2 Dead Band
JUMP TO FULL CODE CHAPTER
Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
Exceptions to 6.4.3.1.2
- Thermostats that require manual changeover between heating and cooling modes.
- Special occupancy or special applications where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the authority having jurisdiction.
Related Code Sections
6.4.3.1.2 Heating, Ventilating, and Air Conditioning, Dead Band
Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > 6 Heating, Ventilating, and Air Conditioning > 6.4 Mandatory Provisions > 6.4.3 Controls and Diagnostics > 6.4.3.1 Zone Thermostatic Controls > 6.4.3.1.2 Dead Band
6.5.2.2 Heating, Ventilating, and Air Conditioning, Hydronic System Controls
both heated and chilled water are acceptable provided all of the following are met: The system is designed to allow a dead band between changeover ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > 6 Heating, Ventilating, and Air Conditioning > 6.5 Prescriptive Compliance Path > 6.5.2 Simultaneous Heating and Cooling Limitation > 6.5.2.2 Hydronic System Controls
6.5.2 Heating, Ventilating, and Air Conditioning, Simultaneous Heating and Cooling Limitation
that comply with all of the following: The airflow rate in dead band between heating and cooling does not exceed the larger of the following: The ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > 6 Heating, Ventilating, and Air Conditioning > 6.5 Prescriptive Compliance Path > 6.5.2 Simultaneous Heating and Cooling Limitation
6.4.3.6.1 Heating, Ventilating, and Air Conditioning, Dehumidification
controls are capable of and configured to maintain a dead band of at least 10% relative humidity where no active humidification or dehumidification ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > 6 Heating, Ventilating, and Air Conditioning > 6.4 Mandatory Provisions > 6.4.3 Controls and Diagnostics > 6.4.3.6 Humidification and Dehumidification Control > 6.4.3.6.1 Dehumidification
6.4.3.1 Heating, Ventilating, and Air Conditioning, Zone Thermostatic Controls
to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°F ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > 6 Heating, Ventilating, and Air Conditioning > 6.4 Mandatory Provisions > 6.4.3 Controls and Diagnostics > 6.4.3.1 Zone Thermostatic Controls