808.3.1 Daylight Prescriptive Requirements
JUMP TO FULL CODE CHAPTER
Daylit areas shall comply with Section 808.3.1.1 or 808.3.1.2. For determining the total daylit area, any overlapping daylit areas shall be counted only once.
The total daylight area shall be the sum of the area of all sidelighting daylight zones and the area of all toplighting zones, except that sidelighting daylight zones shall not be included in the calculation of the area of toplighting daylight areas.
The daylit area shall be illuminated by fenestration that complies with Table 808.3.1.1 and Figure 808.3.1.1(4). Where fenestration is located in a wall, the daylit area shall extend laterally to the nearest 56-inch-high (1422 mm) partition, or up to 1.0 times the height from the floor to the top of fenestration facing within 45 degrees (0.785 rad) of east or west or up to 1.5 times the height from the floor to the top of all other fenestration, whichever is less, and longitudinally from the edge of the fenestration to the nearest 56-inch-high (1422 mm) partition, or up to 2 feet (610 mm), whichever is less, as indicated in Figure 808.3.1.1(1). Where fenestration is located in a rooftop monitor, the daylit area shall extend laterally to the nearest 56-inch-high (1422 mm) partition, or up to 1.0 times the height from the floor to the bottom of the fenestration, whichever is less, and longitudinally from the edge of the fenestration to the nearest 56-inch-high (1422 mm) partition, or up to 0.25 times the height from the floor to the bottom of the fenestration, whichever is less, as indicated in Figures 808.3.1.1(2) and 808.3.1.1(3).
EA = (AF × VT)/DA | (Equation 8-2) |
where:
EA | = | Effective aperture. |
AF | = | Area of fenestration. |
VT | = | Visible transmittance of the fenestration. |
DA | = | Daylit area. |
TABLE 808.3.1.1
MINIMUM EFFECTIVE APERTURE
SKY TYPE | MINIMUM EFFECTIVE APERTURE (percentage) | ||
Sidelighting from fenestration in a wall [see Figure 808.3.1.1(1)] | Sidelighting from rooftop monitor [see Figures 808.3.1.1(2) and 808.3.1.1(3)] | Toplighting (see Figure 808.3.1.2) | |
Aa | 10.0 | 5.0 | 1.0 |
Bb | 12.0 | 6.0 | 1.2 |
Cc | 16.0 | 8.0 | 2.2 |
- Sky Type A — more than 75 percent mean sunshine, in accordance with the NOAA Annual Mean Sunshine Percentage Table.
- Sky Type B — 45 percent to 75 percent mean sunshine, in accordance with the NOAA Annual Mean Sunshine Percentage Table.
- Sky Type C — less than 45 percent mean sunshine, in accordance with the NOAA Annual Mean Sunshine Percentage Table.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.017 rad.
FIGURE 808.3.1.1(1)
DAYLIT AREA ADJACENT TO FENESTRATION IN A WALL
For SI: 1 inch = 25.4 mm.
FIGURE 808.3.1.1(2)
DAYLIT AREA ADJACENT UNDER A ROOFTOP MONITOR
For SI: 1 inch = 25.4 mm.
FIGURE 808.3.1.1(3)
DAYLIT AREA ADJACENT UNDER A ROOFTOP MONITOR
FIGURE 808.3.1.1(4)
SKY TYPES
The daylit area shall be illuminated by a roof fenestration assembly such as a skylight, sloped glazing or tubular daylighting device that complies with Table 808.3.1.1 and Figure 808.3.1.2. The daylit area extends laterally and longitudinally beyond the glazed opening of the roof fenestration assembly to the nearest 56-inch-high (1422 mm) partition, or up to 0.7 times the height from the floor to the bottom of the rough opening of the daylighting well, whichever is less, as indicated in Figure 808.3.1.2.
For SI: 1 inch = 25.4 mm.
FIGURE 808.3.1.2
DAYLIT AREA UNDER A SKYLIGHT
Related Code Sections
808.3.1 Indoor Environmental Quality and Comfort, Daylight Prescriptive Requirements
only once. The total daylight area shall be the sum of the area of all sidelighting daylight zones and the area of all toplighting zones, except ...
Green Construction Code 2012 of Maryland > 8 Indoor Environmental Quality and Comfort > 808 Daylighting > 808.3 Daylit Area of Building Spaces > 808.3.1 Daylight Prescriptive Requirements
C402.4.4 [CE] Commercial Energy Efficiency, Daylight Zones
Daylight zones referenced in Sections C402.4.1.1 through C402.4.3.2 shall comply with Sections C405.2.3.2 and C405.2.3.3, as applicable. Daylight ...
Energy Conservation Code 2018 of Maryland > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Fenestration (Prescriptive) > C402.4.4 Daylight Zones
C402.4 [CE] Commercial Energy Efficiency, Fenestration (Prescriptive)
Exception: Skylights above daylight zones of enclosed spaces are not required in: Buildings in Climate Zones 6 through 8. Spaces where ...
Energy Conservation Code 2015 of Maryland > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Fenestration (Prescriptive)
C402.4.1 [CE] Commercial Energy Efficiency, Maximum Area
fenestration, provided that all of the following requirements are met: In buildings not greater than two stories above grade, not less than 50 ...
Energy Conservation Code 2018 of Maryland > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Fenestration (Prescriptive) > C402.4.1 Maximum Area
C402.4.1.1 [CE] Commercial Energy Efficiency, Increased Vertical Fenestration Area With Daylight Responsive Controls
all of the following requirements are met: In buildings not greater than two stories above grade, not less than 50 percent of the net floor area ...
Energy Conservation Code 2015 of Maryland > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Fenestration (Prescriptive) > C402.4.1 Maximum Area > C402.4.1.1 Increased Vertical Fenestration Area With Daylight Responsive Controls