907.2.3.9.1
An automatic fire alarm system shall be provided in all buildings used as or containing a Group E day-care.
Exception: Automatic detection devices are not required where an approved automatic sprinkler system is installed in accordance with Section 903.3.1.1 and the occupant notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location.
907.2.3.9.2
Smoke detectors shall be installed in every room used for sleeping or napping.