// CODE SNIPPET
1910.66(f)(3)(iii) Davits
JUMP TO FULL CODE CHAPTER
Every davit installation, fixed or transportable, rotatable or non-rotatable shall be designed and installed to insure that it has a stability factor against overturning of not less than four.
The following requirements apply to roof rigged davit systems:
Access to and egress from the working platform shall be from a safe surface. Access or egress shall not require persons to climb over a building's parapet or guard railing; and
The working platform shall be provided with wheels, casters or a carriage for traversing horizontally.
The following requirements apply to ground rigged davit systems:
The point of suspension shall not exceed 300 feet (91.5 m) above a safe surface. Guide system(s) shall be provided which meet the requirements of paragraph (e)(2) of this section;
Access and egress to and from the working platform shall only be from a safe surface below the point of suspension.
A rotating davit shall not require a horizontal force in excess of 40 pounds (177.9 n) per person to initiate a rotating movement.
The following requirements shall apply to transportable davits:
A davit or part of a davit weighing more than 80 pounds (36 kg) shall be provided with a means for its transport, which shall keep the center of gravity of the davit at or below 36 inches (914 mm) above the safe surface during transport;
A davit shall be provided with a pivoting socket or with a base that will allow the insertion or removal of a davit at a position of not more than 35 degrees above the horizontal, with the complete davit inboard of the building face being serviced; and
Means shall be provided to lock the davit to its socket or base before it is used to suspend the platform.
Related Code Sections
1910.66(f)(3)(iii) Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms, Davits
Every davit installation, fixed or transportable, rotatable or non-rotatable shall be designed and installed to insure that it has a stability factor ...
OSHA 1910 General Industry > F Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms > 1910.66 Powered Platforms for Building Maintenance > 1910.66(f) Powered Platform Installations-Equipment > 1910.66(f)(3) Suspension Methods > 1910.66(f)(3)(iii) Davits
1910.66(f)(3)(iii)(D) Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms,
A rotating davit shall not require a horizontal force in excess of 40 pounds (177.9 n) per person to initiate a rotating movement ...
OSHA 1910 General Industry > F Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms > 1910.66 Powered Platforms for Building Maintenance > 1910.66(f) Powered Platform Installations-Equipment > 1910.66(f)(3) Suspension Methods > 1910.66(f)(3)(iii) Davits > 1910.66(f)(3)(iii)(D)
1910.66(f)(3)(iii)(A) Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms,
Every davit installation, fixed or transportable, rotatable or non-rotatable shall be designed and installed to insure that it has a stability factor ...
OSHA 1910 General Industry > F Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms > 1910.66 Powered Platforms for Building Maintenance > 1910.66(f) Powered Platform Installations-Equipment > 1910.66(f)(3) Suspension Methods > 1910.66(f)(3)(iii) Davits > 1910.66(f)(3)(iii)(A)
1910.66(f)(3)(iii)(B) Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms,
The following requirements apply to roof rigged davit systems ...
OSHA 1910 General Industry > F Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms > 1910.66 Powered Platforms for Building Maintenance > 1910.66(f) Powered Platform Installations-Equipment > 1910.66(f)(3) Suspension Methods > 1910.66(f)(3)(iii) Davits > 1910.66(f)(3)(iii)(B)
1910.66(f)(3)(iii)(C) Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms,
The following requirements apply to ground rigged davit systems ...
OSHA 1910 General Industry > F Powered Platforms, Manlifts, and Vehicle-Mounted Work Platforms > 1910.66 Powered Platforms for Building Maintenance > 1910.66(f) Powered Platform Installations-Equipment > 1910.66(f)(3) Suspension Methods > 1910.66(f)(3)(iii) Davits > 1910.66(f)(3)(iii)(C)