701.12 Dampers Prohibited
JUMP TO FULL CODE CHAPTER
Combustion air ducts or
plenums shall not be installed so as to require openings in or
penetrations through construction where fire dampers are
required. Manually operated dampers shall not be installed in
combustion-air openings. With prior approval, power-actuated
movable louvers admitting combustion air shall be
permitted to be used and, where installed, shall be electrically
interlocked with the main burner fuel-supply valve so as to
prevent fuel delivery unless the louvers are in the fully open
position.
Related Code Sections
701.12 Combustion Air, Dampers Prohibited
Combustion air ducts or
plenums shall not be installed so as to require openings in or
penetrations through construction where fire dampers ...
701.12 Combustion Air, Dampers Prohibited
Combustion air ducts or
plenums shall not be installed so as to require openings in or
penetrations through construction where fire dampers ...
A5.207.5.4 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Dampers for Air Supply and Exhaust Equipment
nonelectrical equipment that has readily accessible manual damper controls. At combustion air intakes and shaft vents. Where prohibited by other ...
Los Angeles Green Building Code > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.207 [OSHPD 1, 2 & 4] HVAC Design, Equipment and Installation > A5.207.5 Controls for Space-Conditioning Systems > A5.207.5.4 Dampers for Air Supply and Exhaust Equipment
A5.207.5.4 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Dampers for Air Supply and Exhaust Equipment
nonelectrical equipment that has readily accessible manual damper controls. At combustion air intakes and shaft vents. Where prohibited by other ...
Los Angeles Green Building Code > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.207 [OSHPD 1, 2 & 4] HVAC Design, Equipment and Installation > A5.207.5 Controls for Space-Conditioning Systems > A5.207.5.4 Dampers for Air Supply and Exhaust Equipment
505.6.1 Exhaust Systems, Prohibited
Fire dampers shall not be installed
if the material being exhausted is toxic and if a risk evaluation
indicates that the toxic hazard is greater than ...
Los Angeles Mechanical Code > 5 Exhaust Systems > 505.0 Product-Conveying Systems > 505.6 Fire Dampers > 505.6.1 Prohibited