413.9.2.2 Cylinder Stability
JUMP TO FULL CODE CHAPTER
A method of rigidly supporting the vessel during the venting of CNG shall be provided. The selected method shall provide not less than two points of support and shall prevent horizontal and lateral movement of the vessel. The system shall be designed to prevent movement of the vessel based on the highest gas-release velocity through valve orifices at the vessel's rated pressure and volume. The structure or appurtenance shall be constructed of noncombustible materials.
Related Code Sections
2308.8.1.2.2 Motor Fuel-Dispensing Facilities and Repair Garages, Cylinder Stability
A method of rigidly supporting the vessel during the venting of CNG shall be provided. The selected method shall provide not less than two points ...
Fire Code 2018 of Utah > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2308 Compressed Natural Gas Motor Fuel-Dispensing Facilities > 2308.8 Discharge of CNG From Motor Vehicle Fuel Storage Containers > 2308.8.1 Methods of Discharge > 2308.8.1.2 Atmospheric Venting > 2308.8.1.2.2 Cylinder Stability
413.9.2.2 Gas Piping Installations, Cylinder Stability
A method of rigidly supporting the vessel during the venting of CNG shall be provided. The selected method shall provide not less than two points ...
Fuel Gas Code 2015 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers > 413.9.2 Atmospheric Venting > 413.9.2.2 Cylinder Stability
413.9.2.2 Gas Piping Installations, Cylinder Stability
A method of rigidly supporting the vessel during the venting of CNG shall be provided. The selected method shall provide not less than two points ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers > 413.9.2 Atmospheric Venting > 413.9.2.2 Cylinder Stability
2308.8.1.2 Motor Fuel-Dispensing Facilities and Repair Garages, Atmospheric Venting
The structure or appurtenance used for stabilizing the cylinder shall be separated from the site equipment, features ...
Fire Code 2018 of Utah > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2308 Compressed Natural Gas Motor Fuel-Dispensing Facilities > 2308.8 Discharge of CNG From Motor Vehicle Fuel Storage Containers > 2308.8.1 Methods of Discharge > 2308.8.1.2 Atmospheric Venting
413.9 Gas Piping Installations, Discharge of CNG From Motor Vehicle Fuel Storage Containers
for stabilizing the cylinder shall be separated from the site equipment , features and exposures and shall be located in accordance with Table 413.9.2.3 ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers