2605.2 Cylinder and Container Storage, Handling and Use
JUMP TO FULL CODE CHAPTER
Storage, handling and use of compressed gas cylinders, containers and tanks shall be in accordance with this section and Chapter 30.
The storage or use of a single cylinder of oxygen and a single cylinder of fuel gas located on a cart shall be allowed without requiring the cylinders to be separated in accordance with Section 2703.9.8 or 2703.10.3.6 when the cylinders are connected to regulators, ready for service, equipped with apparatus designed for cutting or welding and all of the following:
- Carts shall be kept away from the cutting or welding operation in accordance with Section 2605.5 or fire-resistant shields shall be provided.
- Cylinders shall be secured to the cart to resist movement.
- Carts shall be in accordance with Section 2703.10.3.
- Cylinder valves not having fixed hand wheels shall have keys, handles or nonadjustable wrenches on valve stems while the cylinders are in service.
- Cylinder valve outlet connections shall conform to the requirements of CGA V-1.
- Cylinder valves shall be closed when work is finished.
- Cylinder valves shall be closed before moving the cart.
Individual carts shall be separated from each other in accordance with Section 2703.9.8.
Related Code Sections
2605.2 Welding and Other Hot Work, Cylinder and Container Storage, Handling and Use
Storage, handling and use of compressed gas cylinders, containers and tanks shall be in accordance with this section and Chapter 30 ...
Fire Code 2009 of Massachusetts > 26 Welding and Other Hot Work > 2605 Gas Welding and Cutting > 2605.2 Cylinder and Container Storage, Handling and Use
3003.5.1 Compressed Gases, Security of Areas
Areas used for the storage, use and handling of compressed gas containers, cylinders, tanks and systems shall be secured against unauthorized entry ...
Fire Code 2009 of Massachusetts > 30 Compressed Gases > 3003 General Requirements > 3003.5 Security > 3003.5.1 Security of Areas
Section 3001 Compressed Gases, General
Storage, use and handling of compressed gases in compressed gas containers, cylinders, tanks and systems shall comply with this chapter ...
3005.10 Compressed Gases, Handling
The handling of compressed gas containers, cylinders and tanks shall comply with Sections 3005.10.1 and 3005.10.2 ...
Fire Code 2009 of Massachusetts > 30 Compressed Gases > 3005 Use and Handling of Compressed Gases > 3005.10 Handling
3704.2 Highly Toxic and Toxic Materials, Indoor Storage and Use
or more gas cabinets or exhausted enclosures shall be provided to handle leaking cylinders, containers or tanks.
Exceptions:
Where cylinders ...
Fire Code 2009 of Massachusetts > 37 Highly Toxic and Toxic Materials > 3704 Highly Toxic and Toxic Compressed Gases > 3704.2 Indoor Storage and Use