Where the path of egress travel includes intervening rooms, areas or spaces, cumulative occupant loads shall be determined in accordance with this section.
1004.2.1 Intervening Spaces or Accessory Areas
Where occupants egress from one or more rooms, areas or spaces through others, the design occupant load shall be the combined occupant load of interconnected accessory or intervening spaces. Design of egress path capacity shall be based on the cumulative portion of occupant loads of all rooms, areas or spaces to that point along the path of egress travel.
1004.2.2 Adjacent Levels for Mezzanines
That portion of the occupant load of a mezzanine with required egress through a room, area or space on an adjacent level shall be added to the occupant load of that room, area or space.
1004.2.3 Adjacent Stories
Other than for the egress components designed for convergence in accordance with Section 1005.6, the occupant load from separate stories shall not be added.

Related Code Sections

1004.2 Means of Egress, Cumulative Occupant Loads
Where the path of egress travel includes intervening rooms, areas or spaces, cumulative occupant loads shall be determined in accordance ...
1004.2 Means of Egress, Cumulative Occupant Loads
Where the path of egress travel includes intervening rooms, areas or spaces, cumulative occupant loads shall be determined in accordance ...
1004.2.3 Means of Egress, Adjacent Stories
Other than for the egress components designed for convergence in accordance with Section 1005.6, the occupant load from separate stories shall ...
1006.3.3.1 Means of Egress, Mixed Occupancies
) or 1006.3.3(2) for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered to be in accordance ...
1006.3.4.1 Means of Egress, Mixed Occupancies
 1006.3.4(1) or 1006.3.4(2) for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered ...