3203.1 Cryogenic Container
JUMP TO FULL CODE CHAPTER
Cryogenic containers shall comply with the requirements of FC 3203.1.1 through 3203.1.3.3 and FC Chapter 27.
Cryogenic containers shall be designed, constructed, operated and maintained in accordance with the ASME Boiler and Pressure Vessel Code or United States Department of Transportation regulations, or as otherwise approved.
Cryogenic containers shall be provided with pressure gauges. The maximum face reading for dial-type gauges shall not be less than 133 percent nor more than 250 percent of the MAWP of the cryogenic container.
Cryogenic containers shall be provided with a liquid level-indicating device. It shall be unlawful to use cryogenic containers with glass liquid level gauges in direct contact with the contents of such containers.
Stationary cryogenic containers located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of Appendix G of the Building Code) shall comply with Section G307.5 of the Building Code.
Cryogenic containers shall be installed upon substantial concrete or masonry foundations or structural steel supports on firm concrete or masonry foundations. Cryogenic containers shall be supported to prevent the concentration of excessive loads on the supporting portion of the shell. Foundations for horizontal cryogenic containers shall be constructed to accommodate expansion and contraction of the cryogenic container. Foundations shall be provided to support the weight of vaporizers and heat exchangers.
When cryogenic container foundations or supports are subject to exposure to temperatures below -130°F (-89.9°C), the foundations or supports shall be constructed of materials to withstand the low-temperature effects of cryogenic fluid spillage.
Portions of cryogenic containers in contact with foundations or saddles shall be painted to protect against corrosion. Precautions shall be taken to avoid or minimize corrosion due to galvanic action.
Fill connection supports shall be designed and maintained to withstand the repeated application of force required to connect and disconnect hoses of cargo tanks.
Related Code Sections
G307.5 Flood-Resistant Construction, Elevation of Certain Tanks and Containers Serving Critical Facilities
tanks, oxygen tanks, and other cryogenic system storage tanks; Hazardous material storage tanks; Stationary compressed gas containers; Stationary ...
NYC Building Code 2014 > G Flood-Resistant Construction > G307 Tanks > G307.5 Elevation of Certain Tanks and Containers Serving Critical Facilities
502.9.3 Exhaust Systems, Cryogenics
Storage areas for stationary or portable containers of cryogenic fluids in any quantity shall be ventilated in accordance with Section 502.8. Indoor ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 502 Required Systems > 502.9 Hazardous Materials—Requirements for Specific Materials > 502.9.3 Cryogenics
502.9.3 Exhaust Systems, Cryogenics
Storage areas for stationary or portable containers of cryogenic fluids in any quantity shall be ventilated in accordance with Section 502.8. Indoor ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 502 Required Systems > 502.9 Hazardous Materials—Requirements for Specific Materials > 502.9.3 Cryogenics
307.4 Use and Occupancy Classification, High-Hazard Group H-2
Buildings and structures containing materials that present a deflagration hazard or a hazard from accelerated burning shall be classified as Group H ...
NYC Building Code 2014 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.4 High-Hazard Group H-2
307.4 Use and Occupancy Classification, High-Hazard Group H-2
Buildings and structures which contain materials that present a deflagration hazard or a hazard from accelerated burning shall be classified as Group ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.4 High-Hazard Group H-2