1203.11 Cross-Linked Polyethylene (PEX) Plastic Tubing
JUMP TO FULL CODE CHAPTER
Joints between cross-linked polyethylene plastic tubing and fittings shall conform to Sections 1203.11.1 and 1203.11.2. Mechanical joints shall conform to Section 1203.3.
When compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Soldering on the metal portion of the system shall be performed at least 18 inches (457 mm) from a plastic-to-metal adapter in the same water line.
Related Code Sections
1203.9 Hydronic Piping, Cross-Linked Polyethylene (PEX) Plastic Tubing
Joints between cross-linked polyethylene plastic tubing and fittings shall conform to Sections 1203.9.1 through 1203.9.3. Mechanical joints shall ...
2020 Minnesota Mechanical Code > 12 Hydronic Piping > 1203 Joints and Connections > 1203.9 Cross-Linked Polyethylene (PEX) Plastic Tubing
1203.11 Hydronic Piping, Cross-Linked Polyethylene (PEX) Plastic Tubing
Joints between cross-linked polyethylene plastic tubing and fittings shall conform to Sections 1203.11.1 and 1203.11.2. Mechanical joints shall ...
Minnesota Mechanical Code 2015 > 12 Hydronic Piping > 1203 Joints and Connections > 1203.11 Cross-Linked Polyethylene (PEX) Plastic Tubing
1210.6.5 Hydronic Piping, Cross-Linked Polyethylene (PEX) Plastic Tubing
Joints between cross-linked polyethylene plastic tubing and fittings shall comply with Sections 1210.6.5.1 and 1210.6.5.2. Mechanical joints shall ...
2020 Minnesota Mechanical Code > 12 Hydronic Piping > 1210 Plastic Pipe Ground-Source Heat Pump Loop Systems > 1210.6 Joints > 1210.6.5 Cross-Linked Polyethylene (PEX) Plastic Tubing