2308.6.6.1 Cripple Wall Bracing in Seismic Design Categories A, B and C
JUMP TO FULL CODE CHAPTER
For the purposes of this section, cripple walls in Seismic Design Categories A, B and C having a stud height exceeding 14 inches (356 mm) shall be considered to be a story and shall be braced in accordance with Table 2308.6.1. Spacing of edge nailing for required cripple wall bracing shall not exceed 6 inches (152 mm) on center along the foundation plate and the top plate of the cripple wall. Nail size, nail spacing for field nailing and more restrictive boundary nailing requirements shall be as required elsewhere in the code for the specific bracing material used.
Related Code Sections
2308.6.6.1 Wood, Cripple Wall Bracing in Seismic Design Categories A, B and C
For the purposes of this section, cripple walls in Seismic Design Categories A, B and C having a stud height exceeding 14 inches (356 mm) shall ...
Building Code 2018 of Illinois > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.6 Cripple Wall Bracing > 2308.6.6.1 Cripple Wall Bracing in Seismic Design Categories A, B and C
2308.6.6.2 Wood, Cripple Wall Bracing in Seismic Design Categories D and E
For the purposes of this section, cripple walls in Seismic Design Categories D and E having a stud height exceeding 14 inches (356 mm) shall ...
Building Code 2018 of Illinois > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.6 Cripple Wall Bracing > 2308.6.6.2 Cripple Wall Bracing in Seismic Design Categories D and E
2308.6.10 Wood, Limitations of Concrete or Masonry Veneer
In Seismic Design Categories B and C, concrete or masonry walls and stone or masonry veneer shall not extend above ...
Building Code 2018 of Illinois > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.10 Limitations of Concrete or Masonry Veneer
1807.1.6.3.2 Soils and Foundations, Seismic Requirements
1807.1.6.3(1) through 1807.1.6.3(4) shall be subject to the following limitations: Seismic Design Categories A and B. No additional seismic ...
Building Code 2018 of Illinois > 18 Soils and Foundations > 1807 Foundation Walls, Retaining Walls and Embedded Posts and Poles > 1807.1 Foundation Walls > 1807.1.6 Prescriptive Design of Concrete and Masonry Foundation Walls > 1807.1.6.3 Masonry Foundation Walls > 1807.1.6.3.2 Seismic Requirements