1607.15 Crane Loads
Go To Full Code Chapter
The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets, of moving bridge cranes and monorail cranes shall include the maximum wheel loads of the crane and the vertical impact, lateral and longitudinal forces induced by the moving crane.
1607.15.1 Maximum Wheel Load
1607.15.2 Vertical Impact Force
The maximum wheel loads of the crane shall be increased by the following percentages to account for the effects of vertical impact or vibration:
Monorail cranes (powered) | 25 percent |
Cab-operated or remotely operated bridge cranes (powered) | 25 percent |
Pendant-operated bridge cranes (powered) | 10 percent |
Bridge cranes or monorail cranes with hand-geared bridge, trolley and hoist | 0 percent |
1607.15.3 Lateral Force
The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction perpendicular to the beam, and shall be distributed with due regard to the lateral stiffness of the runway beam and supporting structure.
1607.15.4 Longitudinal Force
The longitudinal force on crane runway beams, except for bridge cranes with hand-geared bridges, shall be calculated as 10 percent of the maximum wheel loads of the crane. The longitudinal force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction parallel to the beam.
Upcodes Diagrams
Related Code Sections
1607.14 Structural Design, Crane Loads
The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets ...
1607.15 Structural Design, Crane Loads
The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets ...
1607.14.3 Structural Design, Lateral Force
The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity ...
1607.15.1 Structural Design, Maximum Wheel Load
The maximum wheel loads shall be the wheel loads produced by the weight of the bridge, as applicable, plus the sum of the rated capacity ...
1607.15.3 Structural Design, Lateral Force
The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity ...