1211.3 CPVC/AL/CPVC Plastic Pipe and Joints
JUMP TO FULL CODE CHAPTER
Joints
between chlorinated polyvinyl chloride/aluminum/chlorinated
polyvinyl chloride (CPVC/AL/CPVC) pipe or fittings shall be
installed in accordance with one of the following methods:
- Mechanical joints shall include flanged and grooved.
- Solvent cement joints for CPVC/AL/CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accordance with ASTM F493, requiring the use of a primer shall be orange in color. The primer shall be colored and be in accordance with ASTM F656. Listed solvent cement in accordance with ASTM F493 that does not require the use of primers, yellow in color, shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter,1/2 of an inch (15 mm) through 3 inches (80 mm) in diameter. Apply primer where required inside the fitting and to the depth of the fitting on pipe. Apply liberal coat of cement to the outside surface of pipe to depth of fitting and inside of fitting. Place pipe inside fitting to forcefully bottom the pipe in the socket and hold together until joint is set.
Related Code Sections
1211.3 Hydronics, CPVC/AL/CPVC Plastic Pipe and Joints
Joints
between chlorinated polyvinyl chloride/aluminum/chlorinated
polyvinyl chloride (CPVC/AL/CPVC) pipe or fittings shall be
installed ...
California Mechanical Code 2019 > 12 Hydronics > 1211.0 Joints and Connections > 1211.3 CPVC/AL/CPVC Plastic Pipe and Joints
605.3 Water Supply and Distribution, CPVC/AL/CPVC Plastic Pipe and Joints
Chlorinated
polyvinyl chloride/aluminum/chlorinated polyvinyl
chloride (CPVC/AL/CPVC) plastic pipe and fitting joining
methods shall be installed ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.3 CPVC/AL/CPVC Plastic Pipe and Joints
605.3 Water Supply and Distribution, CPVC/AL/CPVC Plastic Pipe and Joints
Chlorinated
polyvinyl chloride/aluminum/chlorinated polyvinyl
chloride (CPVC/AL/CPVC) plastic pipe and fitting joining
methods shall be installed ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.3 CPVC/AL/CPVC Plastic Pipe and Joints