1206.3 Courts
JUMP TO FULL CODE CHAPTER
Courts shall be not less than 3 feet (914 mm) in width. Courts having windows opening on opposite sides shall be not less than 6 feet (1829 mm) in width. Courts shall be not less than 10 feet (3048 mm) in length unless bounded on one end by a public way or yard. For buildings more than two stories above grade plane, the court shall be increased 1 foot (305 mm) in width and 2 feet (610 mm) in length for each additional story. For buildings exceeding 14 stories above grade plane, the required dimensions shall be computed on the basis of 14 stories above grade plane.
Access shall be provided to the bottom of courts for cleaning purposes.
Courts more than two stories in height shall be provided with a horizontal air intake at the bottom not less than 10 square feet (0.93 m2) in area and leading to the exterior of the building unless abutting a yard or public way.
The bottom of every court shall be properly graded and drained to a public sewer or other approved disposal system complying with the International Plumbing Code.
Related Code Sections
1205.3 Interior Environment, Courts
Courts shall be not less than 3 feet (914 mm) in width. Courts having windows opening on opposite sides shall be not less than 6 feet (1829 mm ...
2020 Building Code of New York State > 12 Interior Environment > 1205 Yards or Courts > 1205.3 Courts
1206.3 Interior Environment, Courts
Courts shall be not less than 3 feet (914 mm) in width. Courts having windows opening on opposite sides shall be not less than 6 feet (1829 mm ...
Building Code 2015 of New York State > 12 Interior Environment > 1206 Yards or Courts > 1206.3 Courts
1206.3 Interior Environment, Courts
Courts shall not be less than 3 feet (914 mm) in width. Courts having windows opening on opposite sides shall not be less than 6 feet (1829 mm ...
1024.5 Means of Egress, Egress Courts
Egress courts serving as a portion of the exit discharge in the means of egress system shall comply with the requirements of Section 1024 ...
1024.5 Means of Egress, Egress Courts
Egress courts serving as a portion of the exit discharge in the means of egress system shall comply with the requirements of Section 1024 ...