R606.5.2 Corbel Projection
JUMP TO FULL CODE CHAPTER
The maximum projection of one unit shall not exceed one-half the height of the unit or one-third the thickness at right angles to the wall. The maximum corbeled projection beyond the face of the wall shall not exceed:
Related Code Sections
R606.5.2 Wall Construction, Corbel Projection
maximum corbeled projection beyond the face of the wall shall not exceed: One-half of the wall thickness for multiwythe walls bonded by mortar or grout ...
Los Angeles Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.5 Corbeled Masonry > R606.5.2 Corbel Projection
R606.5.2 Wall Construction, Corbel Projection
maximum corbeled projection beyond the face of the wall shall not exceed: One-half of the wall thickness for multiple-wythe walls bonded by mortar ...
Los Angeles Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.5 Corbeled Masonry > R606.5.2 Corbel Projection
R1003.5 Chimneys and Fireplaces, Corbeling
story of a two-story dwelling, corbeling of chimneys on the exterior of the enclosing walls may equal the wall thickness. The projection of a single ...
Los Angeles Residential Code > 10 Chimneys and Fireplaces > R1003 Masonry Chimneys > R1003.5 Corbeling
2113.5 Masonry, Corbeling
story of a two-story dwelling, corbeling of chimneys on the exterior of the enclosing walls is permitted to equal the wall thickness. The projection ...
2113.5 Masonry, Corbeling
Masonry chimneys shall not be corbeled more than half of the chimney's wall thickness from a wall or foundation, nor shall a chimney be corbeled from ...