610.12.1 Copper Tube Systems
Go To Full Code Chapter
Maximum velocities in copper and copper alloy tube and fitting systems shall not exceed 8 feet per second (ft/s) (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water.
Upcodes Diagrams
Related Code Sections
610.12.1 Water Supply and Distribution, Copper Tube Systems
Maximum velocities in copper and copper alloy tube and fitting systems shall not exceed 8 feet per second (ft/s) (2.4 m/s) in cold water and 5 ft/s ...
1107.5.4 Refrigeration, Copper Tubing Joints
Copper tubing joints used in refrigerating systems containing Group A2, A3, B2 or B3 refrigerants shall be brazed. Soldered joints shall not be used ...
1319.1.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Where Not Required
If medical gas tube in accordance with ASTM B819, Standard Specification for Seamless Copper Tube for Medical Gas Systems, is used for vacuum piping ...
1320.2.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Medical Vacuum Systems
Vacuum systems fabricated from copper tubing shall be permitted to have branch connections made using mechanically formed, drilled, and extruded tee ...