// CODE SNIPPET
1107.5.1 Copper Brazed Field Swaged
Go To Full Code Chapter
The minimum and maximum cup depth of field-fabricated copper brazed swaged fitting connections shall comply with Table 1107.5.1.
TABLE 1107.5.1
COPPER BRAZED SWAGED CUP DEPTHS
FITTING SIZE (inch) | MINIMUM DEPTH (inch) | MAXIMUM DEPTH (inch) |
1/8 | 0.15 | 0.23 |
3/16 | 0.16 | 0.24 |
1/4 | 0.17 | 0.26 |
3/8 | 0.20 | 0.30 |
1/2 | 0.22 | 0.33 |
5/8 | 0.24 | 0.36 |
3/4 | 0.25 | 0.38 |
1 | 0.28 | 0.42 |
11/4 | 0.31 | 0.47 |
11/2 | 0.34 | 0.51 |
2 | 0.40 | 0.60 |
21/2 | 0.47 | 0.71 |
3 | 0.53 | 0.80 |
31/2 | 0.59 | 0.89 |
4 | 0.64 | 0.96 |
For SI: 1 inch = 25.4 mm.