808.0 Cooling Water
JUMP TO FULL CODE CHAPTER
Where permitted by the Authority Having
Jurisdiction, clean running water used exclusively as a
cooling medium in an appliance, device, or apparatus shall
be permitted to discharge into the drainage system through
the inlet side of a fixture trap in the event that a suitable
fixture is not available to receive such discharge. Such trap
connection shall be by means of a pipe connected to the
inlet side of an approved fixture trap, the upper end terminating
in a funnel-shaped receptacle set adjacent, and not
less than 6 inches (152 mm) above the overflow rim of the
fixture.
Related Code Sections
808.0 Indirect Wastes, Cooling Water
Where permitted by the Authority Having
Jurisdiction, clean running water used exclusively as a cooling
medium in an appliance, device, or apparatus ...
808.0 Indirect Wastes, Cooling Water
Where permitted by the Authority Having
Jurisdiction, clean running water used exclusively as a
cooling medium in an appliance, device, or apparatus ...
603.5.8 Water Supply and Distribution, Water-Cooled Equipment
Water-cooled
compressors, degreasers, or other water-cooled equipment
shall be protected by a backflow preventer
installed in accordance ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 603.0 Cross-Connection Control > 603.5 Specific Requirements > 603.5.8 Water-Cooled Equipment
603.5.8 Water Supply and Distribution, Water-Cooled Equipment
Water-cooled
compressors, degreasers, or other water-cooled equipment
shall be protected by a backflow preventer installed
in accordance ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 603.0 Cross-Connection Control > 603.5 Specific Requirements > 603.5.8 Water-Cooled Equipment
217.0 Definitions, -O-
water include,
but are not limited to, gray water; rainwater; stormwater;
reclaimed (recycled) water; cooling tower blow-down water;
and foundation ...