1509.4 Cooling Towers
JUMP TO FULL CODE CHAPTER
Cooling towers in excess of 250 square feet (23.2 m2) in base area or in excess of 15 feet (4572 mm) high where located on building roofs more than 50 feet (15 240 mm) high shall be of noncombustible construction.
Exceptions:
Exceptions:
- Drip boards and the enclosing construction of wood not less than 1 inch (25 mm) nominal thickness, provided the wood is covered on the exterior of the tower with noncombustible material.
- Fill and drift eliminators may be of combustible material if the towers are provided with automatic sprinkler protection complying with Section 903 of this code.
- Fill and drift eliminators that comply with Section 908 of the New York City Mechanical Code.
Related Code Sections
Article *317 Maintenance of Buildings, Cooling Towers
All owners of cooling towers shall comply with this article and the rules of the department ...
1509.4 Roof Assemblies and Rooftop Structures, Cooling Towers
Cooling towers in excess of 250 square feet (23.2 m 2 ) in base area or in excess of 15 feet (4572 mm) high where located on buildings more than 50 ...
NYC Building Code 2008 > 15 Roof Assemblies and Rooftop Structures > 1509 Rooftop Structures > 1509.4 Cooling Towers
1509.4 Roof Assemblies and Rooftop Structures, Cooling Towers
Cooling towers in excess of 250 square feet (23.2 m 2 ) in base area or in excess of 15 feet (4572 mm) high where located on building roofs more than ...
NYC Building Code 2014 > 15 Roof Assemblies and Rooftop Structures > 1509 Rooftop Structures > 1509.4 Cooling Towers
908.4.1 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Cooling Towers
All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing ...
NYC Mechanical Code 2008 > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 908 Cooling Towers, Evaporative Condensers and Fluid Coolers > 908.4 Support and Anchorage > 908.4.1 Cooling Towers
926.2.7 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Cooling Towers
All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing ...
NYC Mechanical Code 2008 > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 926 Noise Control Requirements > 926.2 Minimum Structure-Borne Noise and Vibration Isolation Requirements > 926.2.7 Cooling Towers