Upon activation, the smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing and labeling of appliances used in the system. Air distribution systems that are part of a smoke control system shall switch to the smoke control mode upon activation of a detector.
[F] 606.4.1 Supervision
The duct smoke detectors shall be connected to a fire alarm system where a fire alarm system is required by Section 907.2 of the International Fire Code. The actuation of a duct smoke detector shall activate a visible and audible supervisory signal at a constantly attended location. In facilities that are required to be monitored by a supervising station, duct smoke detectors shall report only as a supervisory signal, not as a fire alarm.
Exceptions:
  1. The supervisory signal at a constantly attended location is not required where the duct smoke detector activates the building's alarm-indicating appliances.
  2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and audible signal in an approved location. Duct smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.

Related Code Sections

606.4 Duct Systems, Controls Operation
Upon activation, the smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing ...
606.4 Duct Systems, Controls Operation
Upon activation, the smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing ...
606.4 Duct Systems, Controls Operation
Upon activation, the smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing ...