Wiring for operation and control of mechanical smoke removal systems shall be connected ahead of the main disconnect in accordance with Section 701.12E of NFPA 70 and be protected against interior fire exposure to temperatures in excess of 1,000°F (538°C) for a period of not less than 15 minutes.
Upcodes Diagrams

Related Code Sections

695.14 Special Equipment, Control Wiring
by the controller manufacturer. Such wiring shall be protected against physical damage. Controller manufacturer's specifications for distance and wire size shall ...
695.14 Special Equipment, Control Wiring
by the controller manufacturer. Such wiring shall be protected against physical damage. Controller manufacturer's specifications for distance and wire size shall ...
910.4.6 Fire Protection and Life Safety Systems, Control Wiring
Wiring for operation and control of mechanical smoke removal systems shall be connected ahead of the main disconnect in accordance with Section ...
910.4.6 Fire Protection and Life Safety Systems, Control Wiring
Wiring for operation and control of mechanical smoke removal systems shall be connected ahead of the main disconnect in accordance with Section ...
(3) Special Conditions, Generator Control Wiring
Control conductors installed between the transfer equipment and the emergency generator shall be kept entirely independent of all other wiring ...