1926.963(e) Control and Measuring Circuits
JUMP TO FULL CODE CHAPTER
The employer may not run control wiring, meter connections, test leads, or cables from a test area unless contained in a grounded metallic sheath and terminated in a grounded metallic enclosure or unless the employer takes other precautions that it can demonstrate will provide employees with equivalent safety.
The employer shall isolate meters and other instruments with accessible terminals or parts from test personnel to protect against hazards that could arise should such terminals and parts become energized during testing. If the employer provides this isolation by locating test equipment in metal compartments with viewing windows, the employer shall provide interlocks to interrupt the power supply when someone opens the compartment cover.
The employer shall protect temporary wiring and its connections against damage, accidental interruptions, and other hazards. To the maximum extent possible, the employer shall keep signal, control, ground, and power cables separate from each other.
If any employee will be present in the test area during testing, a test observer shall be present. The test observer shall be capable of implementing the immediate deenergizing of test circuits for safety purposes.
Related Code Sections
1926.963(e) Electric Power Transmission and Distribution, Control and Measuring Circuits
The employer may not run control wiring, meter connections, test leads, or cables from a test area unless contained in a grounded metallic sheath ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.963 Testing and Test Facilities > 1926.963(e) Control and Measuring Circuits
1926.963(b) Electric Power Transmission and Distribution, General Requirements
and control circuits, and a means providing for periodic safety checks of field test areas ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.963 Testing and Test Facilities > 1926.963(b) General Requirements
1926.417(a) Electrical, Controls
Controls that are to be deactivated during the course of work on energized or deenergized equipment or circuits shall be tagged ...
OSHA 1926 Construction > K Electrical > 1926.417 Lockout and Tagging of Circuits > 1926.417(a) Controls
1926.963 Electric Power Transmission and Distribution, Testing and Test Facilities
and control circuits, and a means providing for periodic safety checks of field test areas ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.963 Testing and Test Facilities
1926.60(o)(4) Occupational Health and Environmental Controls, Exposure Measurements
The employer shall keep an accurate record of all measurements taken to monitor employee exposure to MDA ...
OSHA 1926 Construction > D Occupational Health and Environmental Controls > 1926.60 Methylenedianiline > 1926.60(o) Recordkeeping > 1926.60(o)(4) Exposure Measurements