// CODE SNIPPET
[F] 909.16.3 Control Action and Priorities
JUMP TO FULL CODE CHAPTER
The firefighter's control panel actions shall be as follows:
- ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control point within the building. Once issued from the fire fighter's control panel, automatic or manual control from any other control point within the building shall not contradict the control action. Where automatic means are provided to interrupt normal, nonemergency equipment operation or produce a specific result to safeguard the building or equipment including, but not limited to, duct freezestats, duct smoke detectors, high-temperature cutouts, temperature-actuated linkage and similar devices, such means shall be capable of being overridden by the fire fighter's control panel. The last control action as indicated by each fire fighter's control panel switch position shall prevail. Control actions shall not require the smoke control system to assume more than one configuration at any one time.
Exception: Power disconnects required by NFPA 70.
- Only the AUTO position of each three-position firefighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the NORMAL, nonemergency, building control position. Where a fire fighter's control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described in Section 909.16.1. Where directed by an automatic signal to assume an emergency condition, the NORMAL position shall become the emergency condition for that device or group of devices within the zone. Control actions shall not require the smoke control system to assume more than one configuration at any one time.
Related Code Sections
909.16.3 Fire Protection and Life Safety Systems, Control Action and Priorities
The fire-fighter's control panel actions shall be as follows: ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control ...
2018 South Carolina Building Code > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection Systems, Control Action and Priorities
The fire fighter's control panel actions shall be as follows: ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control ...
2015 South Carolina Fire Code > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection and Life Safety Systems, Control Action and Priorities
The fire fighter's control panel actions shall be as follows: ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control ...
2018 South Carolina Fire Code > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection Systems, Control Action and Priorities
The firefighter's control panel actions shall be as follows:
ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any ...
2015 South Carolina Building Code > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
Section 909 Fire Protection Systems, Smoke Control Systems
The fire fighter's control panel actions shall be as follows: ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control ...