// CODE SNIPPET
R602.10.4 Continuous Sheathing
Go To Full Code Chapter
Braced wall lines with continuous sheathing shall be constructed in accordance with this section. All braced wall lines along exterior walls on the same story shall be continuously sheathed.
Exception: Within Seismic Design Categories A, B and C or in regions where the basic wind speed is less than or equal to 100 mph (45 m/s), other bracing methods prescribed by this code shall be permitted on other braced wall lines on the same story level or on any braced wall line on different story levels of the building.
R602.10.4.1 Continuous Sheathing Braced Wall Panels
Continuous sheathing methods require structural panel sheathing to be used on all sheathable surfaces on one side of a braced wall line including areas above and below openings and gable end walls. Braced wall panels shall be constructed in accordance with one of the methods listed in Table R602.10.4.1. Different bracing methods, other than those listed in Table R602.10.4.1, shall not be permitted along a braced wall line with continuous sheathing.
METHOD | MATERIAL | MINIMUM THICKNESS | FIGURE | CONNECTION CRITERIA |
CS-WSP | Wood structural panel | 3/8" | ![]() |
6d common (2" × 0.113") nails at 6" spacing (panel edges) and at 12" spacing (intermediate supports) or 16 ga. × 13/4 staples at 3" spacing (panel edges) and 6" spacing (intermediate supports) |
CS-G | Wood structural panel adjacent to garage openings and supporting roof load onlya,b | 3/8" | ![]() |
See Method CS-WSP |
CS-PF | Continuous portal frame | See Section R602.10.4.1.1 |
![]() |
See Section R602.10.4.1.1 |
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 47.89 Pa.
- Applies to one wall of a garage only.
- Roof covering dead loads shall be 3 psf or less.
R602.10.4.1.1 Continuous Portal Frame
Continuous portal frame braced wall panels shall be constructed in accordance with Figure R602.10.4.1.1. The number of continuous portal frame panels in a single braced wall line shall not exceed four. For purposes of resisting wind pressures acting perpendicular to the wall, the requirements of Figure R602.10.4.1.1 and Table R602.10.4.1.1 shall be met. There shall be a maximum of two braced wall segments per header and header length shall not exceed 22 feet (6706 mm). Tension straps shall be installed in accordance with the manufacturer's recommendations.
FIGURE R602.10.4.1.1
METHOD CS-PF: CONTINUOUS PORTAL FRAME PANEL CONSTRUCTION
MINIMUM WALL STUD FRAMING NOMINAL SIZE AND GRADE | MAXIMUM PONY WALL HEIGHT (feet) | MAXIMUM TOTAL WALL HEIGHT (feet) |
MAXIMUM OPENING WIDTH (feet) |
BASIC WIND SPEED (mph) | |||||
85 | 90 | 100 | 85 | 90 | 100 | ||||
Exposure B | Exposure C | ||||||||
Tension strap capacity required (lbf)a,b | |||||||||
2 × 4 No. 2 Grade |
0 | 10 | 18 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
1 | 10 | 9 | 1000 | 1000 | 1000 | 1000 | 1000 | 1275 | |
16 | 1000 | 1000 | 1750 | 1800 | 2325 | 3500 | |||
18 | 1000 | 1200 | 2100 | 2175 | 2725 | DR | |||
2 | 10 | 9 | 1000 | 1000 | 1025 | 1075 | 1550 | 2500 | |
16 | 1525 | 2025 | 3125 | 3200 | 3900 | DR | |||
18 | 1875 | 2400 | 3575 | 3700 | DR | DR | |||
2 | 12 | 9 | 1000 | 1200 | 2075 | 2125 | 2750 | 4000 | |
16 | 2600 | 3200 | DR | DR | DR | DR | |||
18 | 3175 | 3850 | DR | DR | DR | DR | |||
4 | 12 | 9 | 1775 | 2350 | 3500 | 3550 | DR | DR | |
16 | 4175 | DR | DR | DR | DR | DR | |||
2 × 6 Stud Grade |
2 | 12 | 9 | 1000 | 1000 | 1325 | 1375 | 1750 | 2550 |
16 | 1650 | 2050 | 2925 | 3000 | 3550 | DR | |||
18 | 2025 | 2450 | 3425 | 3500 | 4100 | DR | |||
4 | 12 | 9 | 1125 | 1500 | 2225 | 2275 | 2775 | 3800 | |
16 | 2650 | 3150 | DR | DR | DR | DR | |||
18 | 3125 | 3675 | DR | DR | DR | DR |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound force = 4.448 N.
- DR = design required.
- Strap shall be installed in accordance with manufacturer's recommendations.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound force = 4.448 N.
METHOD CS-PF: CONTINUOUS PORTAL FRAME PANEL CONSTRUCTION
R602.10.4.2 Length of Braced Wall Panels With Continuous Sheathing
Braced wall panels along a braced wall line with continuous sheathing shall be full-height with a length based on the adjacent clear opening height in accordance with Table R602.10.4.2 and Figure R602.10.4.2. Within a braced wall line when a panel has an opening on either side of differing heights, the taller opening height shall be used to determine the panel length from Table R602.10.4.2. For Method CS-PF, wall height shall be measured from the top of the header to the bottom of the bottom plate as shown in Figure R602.10.4.1.1.
FIGURE R602.10.4.2
BRACED WALL PANELS WITH CONTINUOUS SHEATHING
METHOD |
ADJACENT CLEAR OPENING HEIGHT (inches) |
WALL HEIGHT (feet) | ||||
8 | 9 | 10 | 11 | 12 | ||
CS-WSP | 64 | 24 | 27 | 30 | 33 | 36 |
68 | 26 | 27 | 30 | — | — | |
72 | 28 | 27 | 30 | — | — | |
76 | 29 | 30 | 30 | — | — | |
80 | 31 | 33 | 30 | — | — | |
84 | 35 | 36 | 33 | — | — | |
88 | 39 | 39 | 36 | — | — | |
92 | 44 | 42 | 39 | — | — | |
96 | 48 | 45 | 42 | — | — | |
100 | — | 48 | 45 | — | — | |
104 | — | 51 | 48 | — | — | |
108 | — | 54 | 51 | — | — | |
112 | — | — | 54 | 44 | — | |
116 | — | — | 57 | — | — | |
120 | — | — | 60 | — | — | |
122 | — | — | — | — | 48 | |
132 | — | — | — | 66 | — | |
144 | — | — | — | — | 75 | |
CS-G | ≤ 120 | 24 | 27 | 30 | — | — |
CS-PF | ≤ 120 | 16 | 18 | 20 | — | — |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
- Interpolation shall be permitted.

BRACED WALL PANELS WITH CONTINUOUS SHEATHING
R602.10.4.3 Length of Bracing for Continuous Sheathing
Braced wall lines with continuous sheathing shall be provided with braced wall panels in the length required in Tables R602.10.1.2(1) and R602.10.1.2(2). Only those full-height braced wall panels complying with the length requirements of Table R602.10.4.2 shall be permitted to contribute to the minimum required length of bracing.
R602.10.4.4 Continuously Sheathed Braced Wall Panel Location and Corner Construction
For all continuous sheathing methods, full-height braced wall panels complying with the length requirements of Table R602.10.4.2 shall be located at each end of a braced wall line with continuous sheathing and at least every 25 feet (7620 mm) on center. A minimum 24 inch (610 mm) wood structural panel corner return shall be provided at both ends of a braced wall line with continuous sheathing in accordance with Figures R602.10.4.4(1) and R602.10.4.4(2). In lieu of the corner return, a hold-down device with a minimum uplift design value of 800 pounds (3560 N) shall be fastened to the corner stud and to the foundation or framing below in accordance with Figure R602.10.4.4(3).
FIGURE R602.10.4.4(1)
TYPICAL EXTERIOR CORNER FRAMING FOR CONTINUOUS SHEATHING
FIGURE R602.10.4.4(2)
BRACED WALL LINE WITH CONTINUOUS SHEATHING WITH CORNER RETURN PANEL
FIGURE R602.10.4.4(3)
BRACED WALL LINE WITH CONTINUOUS SHEATHING WITHOUT CORNER RETURN PANEL
FIGURE R602.10.4.4(4)
BRACED WALL LINE WITH CONTINUOUS SHEATHING FIRST BRACED WALL PANEL
AWAY FROM END OF WALL LINE WITHOUT TIE DOWN
FIGURE R602.10.4.4(5)
BRACED WALL LINE WITH CONTINUOUS SHEATHING—FIRST BRACED WALL
PANEL AWAY FROM END OF WALL LINE WITH HOLD-DOWN
Exception:
The first braced wall panel shall be permitted to begin 12.5 feet (3810 mm) from each end of the braced wall line in Seismic Design Categories A, B and C and 8 feet (2438 mm) in Seismic Design Categories D0, D1 and D2 provided one of the following is satisfied:
- A minimum 24 inch (610 mm) long, full-height wood structural panel is provided at both sides of a corner constructed in accordance with Figure R602.10.4.4(1) at the braced wall line ends in accordance with Figure R602.10.4.4(4), or
- The braced wall panel closest to the corner shall have a hold-down device with a minimum uplift design value of 800 pounds (3560 N) fastened to the stud at the edge of the braced wall panel closest to the corner and to the foundation or framing below in accordance with Figure R602.10.4.4(5).

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm.
TYPICAL EXTERIOR CORNER FRAMING FOR CONTINUOUS SHEATHING

For SI: 1 foot = 304.8 mm.
BRACED WALL LINE WITH CONTINUOUS SHEATHING WITH CORNER RETURN PANEL

For SI: 1 inch = 25.4 mm, 1 pound = 4.448 N.
BRACED WALL LINE WITH CONTINUOUS SHEATHING WITHOUT CORNER RETURN PANEL

For SI: 1 inch = 25.4 mm.
BRACED WALL LINE WITH CONTINUOUS SHEATHING FIRST BRACED WALL PANEL
AWAY FROM END OF WALL LINE WITHOUT TIE DOWN

For SI: 1 foot = 305 mm. 1 pound = 4.448 N.
BRACED WALL LINE WITH CONTINUOUS SHEATHING—FIRST BRACED WALL
PANEL AWAY FROM END OF WALL LINE WITH HOLD-DOWN
Upcodes Diagrams
Related Code Sections
R602.10.4 Wall Construction, Continuous Sheathing
Braced wall lines with continuous sheathing shall be constructed in accordance with this section. All braced wall lines along exterior walls ...
R602.10.4.2 Wall Construction, Continuous Sheathing Methods
Continuous sheathing methods require structural panel sheathing to be used on all sheathable surfaces on one side of a braced wall line including ...
R602.10.5.1 Wall Construction, Continuously Sheathed Braced Wall Line Requirements
Continuously-sheathed braced wall lines shall be in accordance with Figure R602.10.4.2 and shall comply with all of the following requirements ...
R602.10.4.4 Wall Construction, Continuously Sheathed Braced Wall Panel Location and Corner Construction
For all continuous sheathing methods, full-height braced wall panels complying with the length requirements of Table R602.10.4.2 shall be located ...
R602.10.4.2 Wall Construction, Length of Braced Wall Panels With Continuous Sheathing
Braced wall panels along a braced wall line with continuous sheathing shall be full-height with a length based on the adjacent clear opening height ...