[F] 415.11.7 Continuous Gas Detection Systems
Go To Full Code Chapter
A continuous gas detection system shall be provided for HPM gases where the physiological warning threshold level of the gas is at a higher level than the accepted permissible exposure limit (PEL) for the gas and for flammable gases in accordance with Sections 415.11.7.1 and 415.11.7.2.
[F] 415.11.7.1 Where Required
A continuous gas detection system shall be provided in the areas identified in Sections 415.11.7.1.1 through 415.11.7.1.4.
[F] 415.11.7.1.1 Fabrication Areas
A continuous gas detection system shall be provided in fabrication areas where gas is used in the fabrication area.
[F] 415.11.7.1.2 HPM Rooms
A continuous gas detection system shall be provided in HPM rooms where gas is used in the room.
[F] 415.11.7.1.3 Gas Cabinets, Exhausted Enclosures and Gas Rooms
A continuous gas detection system shall be provided in gas cabinets and exhausted enclosures. A continuous gas detection system shall be provided in gas rooms where gases are not located in gas cabinets or exhausted enclosures.
[F] 415.11.7.1.4 Corridors
Where gases are transported in piping placed within the space defined by the walls of a corridor and the floor or roof above the corridor, a continuous gas detection system shall be provided where piping is located and in the corridor.
Exception:
A continuous gas detection system is not required for occasional transverse crossings of the corridors by supply piping that is enclosed in a ferrous pipe or tube for the width of the corridor.
[F] 415.11.7.2 Gas Detection System Operation
The continuous gas detection system shall be capable of monitoring the room, area or equipment in which the gas is located at or below all the following gas concentrations:
- Immediately dangerous to life and health (IDLH) values where the monitoring point is within an exhausted enclosure, ventilated enclosure or gas cabinet.
- Permissible exposure limit (PEL) levels where the monitoring point is in an area outside an exhausted enclosure, ventilated enclosure or gas cabinet.
- For flammable gases, the monitoring detection threshold level shall be vapor concentrations in excess of 25 percent of the lower flammable limit (LFL) where the monitoring is within or outside an exhausted enclosure, ventilated enclosure or gas cabinet.
- Except as noted in this section, monitoring for highly toxic and toxic gases shall also comply with Chapter 60 of the International Fire Code.
[F] 415.11.7.2.1 Alarms
The gas detection system shall initiate a local alarm and transmit a signal to the emergency control station when a short-term hazard condition is detected. The alarm shall be both visual and audible and shall provide warning both inside and outside the area where the gas is detected. The audible alarm shall be distinct from all other alarms.
[F] 415.11.7.2.2 Shutoff of Gas Supply
The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for which gas is detected when a short-term hazard condition is detected. Automatic closure of shutoff valves shall comply with the following:
- Where the gas detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.
- Where the gas detection sampling point initiating the gas detection system alarm is within a room and compressed gas containers are not in gas cabinets or an exhausted enclosure, the shutoff valves on all gas lines for the specific gas detected shall automatically close.
- Where the gas detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve supplying the manifold for the compressed gas container of the specific gas detected shall automatically close.
Exception:
Where the gas detection sampling point initiating the gas detection system alarm is at the use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve for the branch line located in the piping distribution manifold enclosure shall automatically close.
Related Code Sections
1803.13 Semiconductor Fabrication Facilities, Continuous Gas Detection Systems
A continuous gas detection system shall be provided for HPM gases when the physiological warning threshold level of the gas is at a higher level than ...
2703.13 Semiconductor Fabrication Facilities, Continuous Gas Detection Systems
A continuous gas detection system shall be provided for HPM gases where the physiological warning threshold level of the gas is at a higher level ...
415.11.7 Special Detailed Requirements Based on Use and Occupancy, Continuous Gas Detection Systems
A continuous gas detection system shall be provided for HPM gases where the physiological warning threshold level of the gas is at a higher level ...
415.8.7 Special Detailed Requirements Based on Use and Occupancy, Continuous Gas Detection Systems
A continuous gas detection system shall be provided for HPM gases when the physiological warning threshold level of the gas is at a higher level than ...
415.8.7.1 Special Detailed Requirements Based on Use and Occupancy, Where Required
A continuous gas detection system shall be provided in the areas identified in Sections 415.8.7.1.1 through 415.8.7.1.4 ...