(C) Continuous
JUMP TO FULL CODE CHAPTER
Except as provided in 250.30(A)(5) and (A)(6), 250.30(B)(1), and 250.68(C), grounding electrode conductor(s) shall be installed in one continuous length without a splice or joint. If necessary, splices or connections shall be made as permitted in (1) through (4):
- Splicing of the wire-type grounding electrode conductor shall be permitted only by irreversible compression-type connectors listed as grounding and bonding equipment or by the exothermic welding process.
- Sections of busbars shall be permitted to be connected together to form a grounding electrode conductor.
- Bolted, riveted, or welded connections of structural metal frames of buildings or structures.
- Threaded, welded, brazed, soldered or bolted-flange connections of metal water piping.
Related Code Sections
1005.4 Means of Egress, Continuity
The capacity of the means of egress required from any story of a building shall not be reduced along the path of egress travel until arrival ...
1005.4 Means of Egress, Continuity
The capacity of the means of egress required from any story of a building shall not be reduced along the path of egress travel until arrival ...
1005.4 Means of Egress, Continuity
The minimum width or required capacity of the means of egress required from any story of a building shall not be reduced along the path of egress ...
1005.4 Means of Egress, Continuity
The minimum width or required capacity of the means of egress required from any story of a building shall not be reduced along the path of egress ...
2020 Minnesota State Fire Code > 10 Means of Egress > 1005 Means of Egress Sizing > 1005.4 Continuity
1009.3.1.3 Means of Egress, Continuity
Exit access stairway enclosures shall have continuity in accordance with Section 707.5.for fire barriers or Section 711.4.for horizontal ...
Minnesota Building Code 2015 > 10 Means of Egress > 1009 Stairways > 1009.3 Exit Access Stairways > 1009.3.1 Construction > 1009.3.1.3 Continuity