1704.3.1 Content of Statement of Special Inspections

Building Code 2015 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of Special Inspections > 1704.3.1 Content of Statement of Special Inspections
JUMP TO FULL CODE CHAPTER
The statement of special inspections shall identify the following:

1. The materials, systems, components and work required to have special inspections or tests by the building official or by the registered design professional responsible for each portion of the work.

2. The type and extent of each special inspection.

3. The type and extent of each test.

4. Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705.11, 1705.12 and 1705.13.

5. For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1704.3.1 Special Inspections and Tests, Content of Statement of Special Inspections
The statement of special inspections shall identify the following: 1. The materials, systems, components and work required to have special ...
Building Code 2015 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of Special Inspections > 1704.3.1 Content of Statement of Special Inspections
1704.3.1 Special Inspections and Tests, Content of statement of special inspections
The statement of special inspections shall identify the following: The materials, systems, components and work required to have special ...
Building Code 2018 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of special inspections > 1704.3.1 Content of statement of special inspections
1704.3.2 Special Inspections and Tests, Seismic requirements in the statement of special inspections
Where Section 1705.12 or 1705.13 specifies special inspections or tests for seismic resistance, the statement of special inspections shall ...
Building Code 2018 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of special inspections > 1704.3.2 Seismic requirements in the statement of special inspections
1704.3.3 Special Inspections and Tests, Wind Requirements in the Statement of Special Inspections
Where Section 1705.11 specifies special inspection for wind resistance, the statement of special inspections shall identify the main windforce ...
Building Code 2015 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of Special Inspections > 1704.3.3 Wind Requirements in the Statement of Special Inspections
1704.3.3 Special Inspections and Tests, Wind requirements in the statement of special inspections
Where Section 1705.11 specifies special inspection for wind resistance, the statement of special inspections shall identify the main windforce ...
Building Code 2018 of Utah > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.3 Statement of special inspections > 1704.3.3 Wind requirements in the statement of special inspections
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US