3104.16.2.2 Containers More Than 500 Gallons
JUMP TO FULL CODE CHAPTER
Portable LP-gas containers with a capacity of more than 500 gallons (1893 L) shall have a minimum separation between the container and structures not less than 25 feet (7620 mm).
Related Code Sections
3104.16.2.2 Tents and Other Membrane Structures, Containers More Than 500 Gallons
Portable LP-gas containers with a capacity of more than 500 gallons (1893 L) shall have a minimum separation between the container and structures ...
Minnesota Fire Code 2015 > 31 Tents and Other Membrane Structures > 3104 Temporary and Permanent Tents and Membrane Structures > 3104.16 LP-gas > 3104.16.2 Location of Containers > 3104.16.2.2 Containers More Than 500 Gallons
6104.3 Liquefied Petroleum Gases, Container Location
-gas containers having a water capacity of less than 125 gallons, is 500 gallons or more, the minimum distance shall comply with the appropriate ...
2020 Minnesota State Fire Code > 61 Liquefied Petroleum Gases > 6104 Location of LP-gas Containers > 6104.3 Container Location
3803.2.1 Higher Education Laboratories, Container Size
The maximum container size for all hazardous materials shall be 5.3 gallons (20 L) for liquids, 50 pounds (22.7 kg) for solids, 100 cubic feet (2.83 ...
2020 Minnesota State Fire Code > 38 Higher Education Laboratories > 3803 General Safety Provisions > 3803.2 Hazardous Materials Storage and Use > 3803.2.1 Container Size
5704.3.6 Flammable and Combustible Liquids, Wholesale and Retail Sales Uses
0.30 3,000 5,000 100 500 2 Containers greater than 5 gallons on pallets or solid pile, one high 0.25 5,000 8,000 100 II Containers ...
2020 Minnesota State Fire Code > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.3 Container and Portable Tank Storage > 5704.3.6 Wholesale and Retail Sales Uses