(D) Contact Conductors
Go To Full Code Chapter
Contact wires shall have an ampacity not less than that required by Table 610.14(A) for 75°C (167°F) wire, and in no case shall they be smaller than as shown in Table 610.14(D).
Table 610.14(D) Minimum Contact Conductor Size Based on Distance Between Supports
Minimum Size of Wire (AWG) | Maximum Distance Between End Strain Insulators or Clamp-Type Intermediate Supports |
---|---|
6 | 9.0 m (30 ft) or less |
4 | 18 m (60 ft) or less |
2 | Over 18 m (60 ft) |