§27-521.12 Construction; General
JUMP TO FULL CODE CHAPTER
(a) A mall may be constructed only in buildings in noncombustible construction groups 1-A, 1-B and 1-C.
(b) The minimum horizontal clear dimension at any level in a mall shall be twenty feet.
(c) Where different tenancies have openings to a mall the tenancies shall be separated in accordance with section 27-341 of article five of subchapter five of this chapter.
(d) All openings between a mall and other spaces shall be provided with a noncombustible draft curtain that shall extend downward a minimum of twenty-four inches below the lowest ceiling adjacent to such draft curtain or shall meet the requirements of clause three of subparagraph d of paragraph three of subdivision (h) of section 27-370 of article five of subchapter six of this chapter relating to show windows.
(b) The minimum horizontal clear dimension at any level in a mall shall be twenty feet.
(c) Where different tenancies have openings to a mall the tenancies shall be separated in accordance with section 27-341 of article five of subchapter five of this chapter.
(d) All openings between a mall and other spaces shall be provided with a noncombustible draft curtain that shall extend downward a minimum of twenty-four inches below the lowest ceiling adjacent to such draft curtain or shall meet the requirements of clause three of subparagraph d of paragraph three of subdivision (h) of section 27-370 of article five of subchapter six of this chapter relating to show windows.
Related Code Sections
§27-521.12 Special Uses and Occupancies, Construction; General
(a) A mall may be constructed only in buildings in noncombustible construction groups 1-A, 1-B and 1-C. (b) The minimum horizontal clear dimension ...
NYC 1968 Code (Vol I) > 7 Special Uses and Occupancies > 22 Malls > §27-521.12 Construction; General
3101.1 Special Construction, Scope
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways ...
3101.1 Special Construction, Scope
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways ...
601.1 Types of Construction, Scope
The provisions of this chapter shall control the classification of buildings as to type of construction with respect to occupancy and exterior fire ...
601.1 Types of Construction, Scope
The provisions of this chapter shall control the classification of buildings as to type of construction ...