// CODE SNIPPET

Article 14 Construction Classifications

NYC 1968 Code (Vol I) > 3 Occupancy and Construction Classification > 14 Construction Classifications
JUMP TO FULL CODE CHAPTER

§27-269 Construction Classes

Table 3-3 lists construction classes that shall be established for classifying buildings and spaces by construction in accordance with the provisions of articles fifteen, sixteen and seventeen of this subchapter.

TABLE 3-3 CONSTRUCTION CLASSES
Construction Group Class
I-Noncombustible I-A— (4-hr. protected)
I-B— (3-hr. protected)
I-C— (2-hr. protected)
I-D— (1-hr. protected)
I-E— (unprotected)
II-Combustible II-A— (heavy timber)
II-B— (protected wood joist)
II-C— (unprotected wood joist)
II-D— (protected wood frame)
II-E— (unprotected wood frame)

§27-270 Classification of Buildings and Spaces

Every building, room, or space hereafter altered or erected shall, for the purposes of this code be classified in one of the construction classes listed in table 3-3.

§27-271 Classification Table

tppn
Linked Resources Available

This section has been clarified by a tppn issued by the Department of Buildings.

Learn more in the Linked Resources panel on the right.
The fire-resistance ratings of construction elements in hours listed in table 3-4 shall be used as a basis for classifying buildings and spaces by construction. Fire-resistance ratings shall be based on the test procedures of reference standard RS3-1 and shall apply to all occupancy groups except as specifically noted. For hazardous occupancies involving an exceptionally high degree of fire risk or an exceptionally high concentration of combustible or flammable contents, the commissioner may increase the requirements of table 3-4.

Notes:

a. The area of openings permitted in exterior walls at any story shall be obtained by multiplying the percentage shown in the table by the exterior separation distance in feet, and then multiplying that product by the square-foot area of the facade of that story. Requirements for protected exterior openings shall not apply to churches or to buildings classified in occupancy groups J-2 and J-3. See section 27-331 of article four of subchapter five of this chapter for additional requirements for exterior walls and exterior wall openings.

b. Upon special application, the commissioner may permit exterior wall openings to be constructed in excess of the permitted area established by table 3-4 if such openings at the time of their construction are located at least sixty feet in a direct line from any neighboring building except as otherwise permitted by footnote f. Such additional openings may not, however, be credited toward meeting any of the mandatory natural light or ventilation requirements of subchapter twelve of chapter one of this title. If any neighboring building is later altered or constructed to come within the above distance limitation, the affected exterior openings shall immediately be closed with construction meeting the fire-resistance rating requirements for exterior wall construction of the building in which they are located.

c. Applies to occupancy groups A, B-1, B-2, and D-1.

d. Applies to all occupancy groups other than those described in footnote c.

††e. See subdivision (i) of section 27-375 of article five of subchapter six of this chapter for additional impact resistance requirements applicable to certain stair enclosures and for certain exceptions to stair enclosure requirements.

f. When two or more buildings are constructed on the same lot, and the combined floor area of the buildings does not exceed the limits estab- lished by tables 4-1 and 4-2 for any one of the buildings, no fire-resistance rating shall be required for nonbearing portions of the exterior walls of those buildings facing each other, and there shall be no limitation on the permitted amount of exterior openings.

g. Fire retardant treated wood complying with the requirements of section 27-328 of article three of subchapter five of this chapter may be used.

h. Tabulated ratings apply to buildings over one story in height. In one story buildings roof construction may be of material having 0 hour fire-resistance rating.

i. Materials which are not noncombustible, as defined in subchapter two of chapter one of this title, may be used in nonbearing construction elements if they fall into one of the following categories:
  1. Materials having a structural base of noncombustible material as defined in subchapter two, and having a surface not over one-eighth inch thick which when tested in accordance with the provisions of reference standard RS 3-2 has a flame spread rating not higher than fifty.
  2. Materials which when tested in accordance with the provisions of reference standard RS 3-2 have a surface flame spread rating not higher than twenty-five without evidence of continued progressive combustion, and which are of such composition that surfaces which would be exposed by cutting through the material in any way would not have a flame spread rating higher than twenty-five without evidence of continued progressive combustion.
j. Applies to the construction of the street floor and all construction below the level of the street floor in buildings or spaces classified in occupancy group J-2 except where the space below the street floor does not exceed five feet in height.

k. Columns supporting the roof of a one-story building shall have the same fire-resistance rating as required for a column supporting one floor in a building of the same construction class.

l. Members supporting loads of not more than two floors or one floor and a roof need not have a fire-resistance rating greater than the floor construction fire-resistance requirement in buildings classified in occupancy groups G, H, and J-2, not including unsprinklered spaces of other occupancies, and in fully sprinklered buildings in occupancy groups E and J-1.

††m. See subdivision (c) of section 27-987 of article one of subchapter eighteen of this chapter for additional impact resistance requirements applicable to certain elevator enclosures.

† Local Law 77-1988.
†† Local Law 26-2004.

§27-272 False Designation

No building or space shall be designated a given construction class unless it conforms to the minimum requirements for that class; and no building or space shall be posted, used, designated, or advertised as of a given construction class unless it complies with the minimum requirements of this code for that class.

§27-273 Minimum Requirements

When a class of construction is utilized which is superior to that required for any particular use, nothing in this code shall be construed to require full compliance with the requirements for the higher class; the designated construction classification of the building or space shall be that of the lesser classification, unless all of the requirements for the higher class are met.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Article 14 Occupancy and Construction Classification, Construction Classifications
Table 3-3 lists construction classes that shall be established for classifying buildings and spaces by construction in accordance with the provisions ...
NYC 1968 Code (Vol I) > 3 Occupancy and Construction Classification > 14 Construction Classifications
Section 602 Types of Construction, Construction Classification
Classification shall be that of the minimum requirement unless all of the requirements for the higher type of construction are met. Exception ...
NYC Building Code 2014 > 6 Types of Construction > 602 Construction Classification
Section 602 Types of Construction, Construction Classification
to a higher type of construction. Classification shall be that of the minimum requirement unless all of the requirements for the higher type of construction ...
NYC Building Code 2008 > 6 Types of Construction > 602 Construction Classification
Subchapter 3 Occupancy and Construction Classification
NYC 1968 Code (Vol I) > 3 Occupancy and Construction Classification
Reference Standard 3 Occupancy and Construction Classifications [PDF] (page 1)
Reference Standard 3 REFERENCE STANDARD RS-3 OCCUPANCY AND CONSTRUCTION CLASSIFICATIONS *LIST OF REFERENCED NATIONAL STANDARDS ASTM E119 Standard ...
NYC 1968 Code (Vol II) [PDF] > Classifications Reference Standard 3 Occupancy and Construction Classifications
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US