Section CC104 Consideration of Existing Fire Hydrants
JUMP TO FULL CODE CHAPTER
Existing fire hydrants on public streets are allowed to be considered as available. Existing fire hydrants on adjacent properties shall not be considered available unless fire apparatus access roads extend between properties and easements are established to prevent obstruction of such roads.
Related Code Sections
Section C104 Fire Hydrant Locations and Distribution, Consideration of Existing Fire Hydrants
Existing fire hydrants on public streets are allowed to be considered as available to meet the requirements of Sections C102 and C103. Existing fire ...
California Fire Code 2019 > C Fire Hydrant Locations and Distribution > C104 Consideration of Existing Fire Hydrants
Section C104 Fire Hydrant Locations and Distribution, Consideration of Existing Fire Hydrants
Existing fire hydrants on public streets are allowed to be considered as available to meet the requirements of Sections C102 and C103. Existing fire ...
California Fire Code 2016 > C Fire Hydrant Locations and Distribution > C104 Consideration of Existing Fire Hydrants
Section CC104 Fire Hydrant Locations and Distribution, Consideration of Existing Fire Hydrants
Existing fire hydrants on public streets are allowed to be considered as available. Existing fire hydrants on adjacent properties shall ...
California Fire Code 2019 > CC Fire Hydrant Locations and Distribution > CC104 Consideration of Existing Fire Hydrants
Section CC104 Fire Hydrant Locations and Distribution, Consideration of Existing Fire Hydrants
Existing fire hydrants on public streets are allowed to be considered as available. Existing fire hydrants on adjacent properties shall ...
California Fire Code 2016 > CC Fire Hydrant Locations and Distribution > CC104 Consideration of Existing Fire Hydrants
Section C103 Fire Hydrant Locations and Distribution, Fire Hydrant Spacing
shall be permitted to be increased by 10 percent where existing fire hydrants provide all or a portion of the required number of fire hydrants ...