G2428.3.3 (504.3.3) Connectors With Longer Lengths
JUMP TO FULL CODE CHAPTER
Connectors with longer horizontal lengths than those listed in Section
G2428.3.2G2429.3.2 are permitted under the following conditions:
- The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section G2428.3.2.G2429.3.2. For example, the maximum length listed in Table G2428.3.2Table G2429.3.2 for a 4-inch (102 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet (1829 mm) but not exceeding 12 feet (3658 mm), the maximum capacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet (3658 mm), but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent (0.80 × maximum vent capacity).
- For a connector serving a fan-assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single-appliance table. For Type B double-wall connectors, Table G2428.2(1)Table G2429.2(1) shall be used. For single-wall connectors, Table G2428.2(2)Table G2429.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single-appliance vent, as if the other appliances were not present.
Related Code Sections
603.6.2.1 Duct Systems, Connector Length
Flexible air connectors shall be limited in length to 14 feet (4267 mm) ...
2014 Oregon Mechanical Specialty Code (OMSC) > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors > 603.6.2 Flexible Air Connectors > 603.6.2.1 Connector Length
603.6.2.1 Duct Systems, Connector Length
Flexible air connectors shall be limited in length to 14 feet (4267 mm) ...
2019 Oregon Mechanical Specialty Code > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors > 603.6.2 Flexible Air Connectors > 603.6.2.1 Connector Length
M1803.3.2 Chimneys and Vents, Length
The horizontal run of an uninsulated connector to a natural draft chimney shall not exceed 75 percent of the height of the vertical portion ...
2017 Oregon Residential Specialty Code (ORSC) > 18 Chimneys and Vents > M1803 Chimney and Vent Connectors > M1803.3 Installation > M1803.3.2 Length
803.10.2 Chimneys and Vents, Length
The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent ...
2014 Oregon Mechanical Specialty Code (OMSC) > 8 Chimneys and Vents > 803 Connectors > 803.10 Installation > 803.10.2 Length
803.10.2 Chimneys and Vents, Length
The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent ...
2019 Oregon Mechanical Specialty Code > 8 Chimneys and Vents > 803 Connectors > 803.10 Installation > 803.10.2 Length