Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 706 Connections Between Drainage Piping and Fittings

Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 706 Connections Between Drainage Piping and Fittings
JUMP TO FULL CODE CHAPTER

706.1 Connections and Changes in Direction

Connections and changes in direction of the sanitary drainage system shall be made with approved drainage fittings. Connections between drainage piping and fixtures shall conform to Section 405.

706.2 Obstructions

The fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow in the piping. Threaded drainage pipe fittings shall be of the recessed drainage type. This section shall not be applicable to tubular waste fittings used to convey vertical flow upstream of the trap seal liquid level of a fixture trap.

706.3 Installation of Fittings

Fittings shall be installed to guide sewage and waste in the direction of flow. Change in direction shall be made by fittings installed in accordance with Table 706.3. Change in direction by combination fittings, side inlets or increasers shall be installed in accordance with Table 706.3 based on the pattern of flow created by the fitting. Double sanitary tee patterns shall not receive the discharge of back-to-back water closets and fixtures or appliances with pumping action discharge.
Exception: Back-to-back water closet connections to double sanitary tees shall be permitted where the horizontal developed length between the outlet of the water closet and the connection to the double sanitary tee pattern is 18 inches (457 mm) or greater.
TABLE 706.3
FITTINGS FOR CHANGE IN DIRECTION
TYPE OF FITTING
PATTERN
CHANGE IN DIRECTION
Horizontal to
vertical
Vertical to
horizontal
Horizontal to
horizontal
Sixteenth bendXXX
Eighth bendXXX
Sixth bendXXX
Quarter bendXXaXa
Short sweepXXa,bXa
Long sweepXXX
Sanitary teeXc——
WyeXXX
Combination wye
and eighth bend
XXX
For SI: 1 inch = 25.4 mm.
  1. The fittings shall only be permitted for a 2-inch or smaller fixture drain.
  2. Three inches or larger.
  3. For a limitation on double sanitary tees, see Section 706.3.

706.4 Heel- or Side-Inlet Quarter Bends

Heel-inlet quarter bends shall be an acceptable means of connection, except where the quarter bend serves a water closet. A low-heel inlet shall not be used as a wet-vented connection. Side-inlet quarter bends shall be an acceptable means of connection for drainage, wet venting and stack venting arrangements.

Related Code Sections


Section 706 Sanitary Drainage, Connections Between Drainage Piping and Fittings
Connections and changes in direction of the sanitary drainage system shall be made with approved drainage fittings. Connections between drainage ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 706 Connections Between Drainage Piping and Fittings
Section P3003 Sanitary Drainage, Joints and Connections
Joints between cast-iron pipe or fittings shall comply with Sections P3003.4.1 through P3003.4.3 ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3003 Joints and Connections
P3005.2.1 Sanitary Drainage, Horizontal Drains and Building Drains
length of the piping to the next drainage fitting providing access for cleaning, the end of the horizontal drain or the end of the building drain ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3005 Drainage System > P3005.2 Cleanouts Required > P3005.2.1 Horizontal Drains and Building Drains
P3005.1 Sanitary Drainage, Drainage Fittings and Connections
Changes in direction in drainage piping shall be made by the appropriate use of sanitary tees, wyes, sweeps, bends or by a combination ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3005 Drainage System > P3005.1 Drainage Fittings and Connections
708.1.1 Sanitary Drainage, Horizontal Drains and Building Drains
length of the piping to the next drainage fitting providing access for cleaning, the end of the horizontal drain or the end of the building drain ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 708 Cleanouts > 708.1 Cleanouts Required > 708.1.1 Horizontal Drains and Building Drains
Help Contact Us Privacy Terms
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING