// CODE SNIPPET
660.4 Connection to Supply Circuit
Go To Full Code Chapter
(A) Fixed and Stationary Equipment
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method meeting the general requirements of this Code. Equipment properly supplied by a branch circuit rated at not over 30 amperes shall be permitted to be supplied through a suitable attachment plug cap and hard-service cable or cord.
(B) Portable, Mobile, and Transportable Equipment
Individual branch circuits shall not be required for portable, mobile, and transportable X-ray equipment requiring a capacity of not over 60 amperes. Portable and mobile types of X-ray equipment of any capacity shall be supplied through a suitable hard-service cable or cord. Transportable X-ray equipment of any capacity shall be permitted to be connected to its power supply by suitable connections and hard-service cable or cord.
(C) Over 1000 Volts, Nominal
Circuits and equipment operated at more than 1000 volts, nominal, shall comply with Article 490.
Upcodes Diagrams
Related Code Sections
517.71 Special Occupancies, Connection to Supply Circuit
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method complying with applicable requirements ...
517.71 Special Occupancies, Connection to Supply Circuit
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method complying with applicable requirements ...
660.4 Special Equipment, Connection to Supply Circuit
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method meeting the general requirements of this Code ...
660.4 Special Equipment, Connection to Supply Circuit
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method meeting the general requirements of this Code ...
(A) Special Occupancies, Fixed and Stationary Equipment
Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method complying with applicable requirements ...