P3107.3 Connection at Different Levels
JUMP TO FULL CODE CHAPTER
Where the fixture drains connect at different levels, the vent shall connect as a vertical extension of the vertical drain. The vertical drain pipe connecting the two fixture drains shall be considered to be the vent for the lower fixture drain, and shall be sized in accordance with Table P3107.3. The upper fixture shall not be a water closet.
COMMON VENT SIZES
PIPE SIZE (inches) | MAXIMUM DISCHARGE FROM UPPER FIXTURE DRAIN (d.f.u.) |
11/2 | 1 |
2 | 4 |
21/2 to 3 | 6 |
For SI: 1 inch = 25.4 mm.
Related Code Sections
911.3 Vents, Connection at Different Levels
Where the fixture drains connect at different levels, the vent shall connect as a vertical extension of the vertical drain. The vertical drain pipe ...
P3107.3 Vents, Connection at Different Levels
Where the fixture drains connect at different levels, the vent shall connect as a vertical extension of the vertical drain. The vertical drain pipe ...
Residential Code 2018 of Kansas > 31 Vents > P3107 Common Vent > P3107.3 Connection at Different Levels
503.5.7.2 Chimneys and Vents, Liquid Fuel-Burning Appliances
are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped ...
Fuel Gas Code 2018 of Kansas > 5 Chimneys and Vents > 503 (IFGS) Venting of Appliances > 503.5 Masonry, Metal and Factory-Built Chimneys > 503.5.7 Chimneys Serving Appliances Burning Other Fuels > 503.5.7.2 Liquid Fuel-Burning Appliances
G2427.5.6.2 Fuel Gas, (503.5.7.2) Liquid Fuel-Burning Appliances
openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2427 (503) Venting of Appliances > G2427.5 (503.5) Masonry, Metal and Factory-Built Chimneys > G2427.5.6 (503.5.7) Chimneys Serving Appliances Burning Other Fuels > G2427.5.6.2 (503.5.7.2) Liquid Fuel-Burning Appliances
G2427.5.6 Fuel Gas, (503.5.7) Chimneys Serving Appliances Burning Other Fuels
into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safety shutoff ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2427 (503) Venting of Appliances > G2427.5 (503.5) Masonry, Metal and Factory-Built Chimneys > G2427.5.6 (503.5.7) Chimneys Serving Appliances Burning Other Fuels