• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects General Contractor Building Official & Plans Examiner Inspectors Owner Subcontractors Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

411.1 Connecting Appliances

2014 FBC - Fuel Gas, 5th edition > 4 Gas Piping Installations > 411 (IFGC) Appliance and Manufactured Home Connections > 411.1 Connecting Appliances
JUMP TO FULL CODE CHAPTER

Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following:

  1. Rigid metallic pipe and fittings.
  2. Corrugated stainless steel tubing (CSST) where installed in accordance with the manufacturer's instructions.
  3. Semirigid metallic tubing and metallic fittings. Lengths shall not exceed 6 feet (1829 mm) and shall be located entirely in the same room as the appliance. Semirigid metallic tubing shall not enter a motor-operated appliance through an unprotected knockout opening.
  4. Listed and labeled appliance connectors in compliance with ANSI Z21.24 and installed in accordance with the manufacturer's instructions and located entirely in the same room as the appliance.
  5. Listed and labeled quick-disconnect devices used in conjunction with listed and labeled appliance connectors.
  6. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance connectors.
  7. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer's instructions.

411.1.1 Commercial Cooking Appliances

Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.69 or in accordance with Item 1 or 3 of Section 411.1.

411.1.2 Protection Against Damage

Connectors and tubing shall be installed so as to be protected against physical damage.

411.1.3 Connector Installation

Appliance fuel connectors shall be installed in accordance with the manufacturer's instructions and Sections 411.1.3.1 through 411.1.3.4.

411.1.3.1 Maximum Length

Connectors shall have an overall length not to exceed 6 feet (1829 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance.

Exception: Rigid metallic piping used to connect an appliance to the piping system shall be permitted to have a total length greater than 6 feet (1829 mm), provided that the connecting pipe is sized as part of the piping system in accordance with Section 402 and the location of the appliance shutoff valve complies with Section 409.5.

411.1.3.2 Minimum Size

Connectors shall have the capacity for the total demand of the connected appliance.

411.1.3.3 Prohibited Locations and Penetrations

Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings.

Exceptions:
  1. Connectors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2 or 409.5.3.
  2. Rigid steel pipe connectors shall be permitted to extend through openings in appliance housings.
  3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in accordance with the listing of the appliance.
  4. Semirigid tubing and listed connectors shall be permitted to extend through an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage.

411.1.3.4 Shutoff Valve

A shutoff valve not less than the nominal size of the connector shall be installed ahead of the connector in accordance with Section 409.5.

411.1.4 Movable Appliances

Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an approved flexible connector designed and labeled for the application. Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer's installation instructions.

411.1.5 (IFGS) Connection of Gas Engine-Powered Air Conditioners

Internal combustion engines shall not be rigidly connected to the gas supply piping.

411.1.6 Unions

A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet (1829 mm) of the appliance.

Related Code Sections


411.1 Gas Piping Installations, Connecting Appliances
Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: Rigid metallic pipe ...
2020 FBC - Fuel Gas, 7th edition > 4 Gas Piping Installations > 411 (IFGC) Appliance and Manufactured Home Connections > 411.1 Connecting Appliances
411.1 Gas Piping Installations, Connecting Appliances
Except as required by Section 411.1.1, appliance s shall be connected to the piping system by one of the following: Rigid metallic pipe ...
2017 FBC - Fuel Gas, 6th edition > 4 Gas Piping Installations > 411 (IFGC) Appliance and Manufactured Home Connections > 411.1 Connecting Appliances
411.1 Gas Piping Installations, Connecting Appliances
Except as required by Section 411.1.1, appliance s shall be connected to the piping system by one of the following: Rigid metallic pipe ...
2014 FBC - Fuel Gas, 5th edition > 4 Gas Piping Installations > 411 (IFGC) Appliance and Manufactured Home Connections > 411.1 Connecting Appliances
G2422.1 Fuel Gas, (411.1) Connecting Appliances
Appliances shall be connected to the piping system by one of the following: Rigid metallic pipe and fittings. Corrugated stainless steel ...
2020 FBC - Residential, 7th edition > 24 Fuel Gas > G2422 (411) Appliance Connections > G2422.1 (411.1) Connecting Appliances
G2422.1 Fuel Gas, (411.1) Connecting Appliances
Appliances shall be connected to the piping system by one of the following: Rigid metallic pipe and fittings. Corrugated stainless steel ...
2014 FBC - Residential, 5th edition > 24 Fuel Gas > G2422 (411) Appliance Connections > G2422.1 (411.1) Connecting Appliances
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE