1910.304(c)(1) Conductors on Poles
JUMP TO FULL CODE CHAPTER
Conductors on poles shall have a separation of not less than 305 mm (1.0 ft) where not placed on racks or brackets. Conductors supported on poles shall provide a horizontal climbing space not less than the following:
Power conductors below communication conductors -- 762 mm (30 in.);
Communication conductors below power conductors -- same as power conductors; and
Communications conductors alone -- no requirement.
Power conductors alone or above communication conductors:
Related Code Sections
1910.304(c)(1) Electrical, Conductors on Poles
Conductors on poles shall have a separation of not less than 305 mm (1.0 ft) where not placed on racks or brackets. Conductors supported on poles ...
OSHA 1910 General Industry > S Electrical > 1910.304 Wiring Design and Protection > 1910.304(c) Outside Conductors, 600 Volts, Nominal, or Less > 1910.304(c)(1) Conductors on Poles
1910.269(q)(1)(ii) Special Industries,
When a pole is set, moved, or removed near an exposed energized overhead conductor, the pole may not contact the conductor ...
OSHA 1910 General Industry > R Special Industries > 1910.269 Electric Power Generation, Transmission, and Distribution > 1910.269(q) Overhead Lines and Live-Line Barehand Work > 1910.269(q)(1) General > 1910.269(q)(1)(ii)
1910.304(c)(1)(iv) Electrical,
Communications conductors alone -- no requirement ...
OSHA 1910 General Industry > S Electrical > 1910.304 Wiring Design and Protection > 1910.304(c) Outside Conductors, 600 Volts, Nominal, or Less > 1910.304(c)(1) Conductors on Poles > 1910.304(c)(1)(iv)
1910.269(q)(1) Special Industries, General
When a pole is set, moved, or removed near an exposed energized overhead conductor, the employer shall ensure that each employee wears ...
OSHA 1910 General Industry > R Special Industries > 1910.269 Electric Power Generation, Transmission, and Distribution > 1910.269(q) Overhead Lines and Live-Line Barehand Work > 1910.269(q)(1) General
1910.265(d)(1)(ii)(j) Special Industries,
electrical conductors. Defective, blunt, or dull pike poles shall not be used ...
OSHA 1910 General Industry > R Special Industries > 1910.265 Sawmills > 1910.265(d) Log Handling, Sorting, and Storage > 1910.265(d)(1) Log Unloading Methods, Equipment, and Facilities > 1910.265(d)(1)(ii) Unloading Equipment and Facilities > 1910.265(d)(1)(ii)(j)