R337.7.3.1 Conditions of Acceptance When Tested in Accordance With ASTM E2707
JUMP TO FULL CODE CHAPTER
The ASTM E2707 test
shall be conducted on a minimum of three test specimens
and the conditions of acceptance in 1 and 2 below
shall be met. If any one of the three tests does not meet
the conditions of acceptance, three additional tests
shall be run. All of the additional tests shall meet the
conditions of acceptance.
- Absence of flame penetration through the wall assembly at any time.
- Absence of evidence of glowing combustion on the interior surface of the assembly at the end of the 70-minute test.
Related Code Sections
707A.3.1 [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Conditions of Acceptance When Tested in Accordance With ASTM E2707
The ASTM E2707 test shall be
conducted on a minimum of three test specimens and the
conditions of acceptance in Items 1 and 2 below shall be met.
If ...
Los Angeles Building Code > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 707A Exterior Covering > 707A.3 Exterior Walls > 707A.3.1 Conditions of Acceptance When Tested in Accordance With ASTM E2707
R337.7.3.1 Building Planning, Conditions of Acceptance When Tested in Accordance With ASTM E2707
The ASTM E2707 test
shall be conducted on a minimum of three test specimens
and the conditions of acceptance in 1 and 2 below
shall be met. If any ...
Los Angeles Residential Code > 3 Building Planning > R337.7 Exterior Covering > R337.7.3 Exterior Walls > R337.7.3.1 Conditions of Acceptance When Tested in Accordance With ASTM E2707
Section 709A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Decking
The material shall be tested in
accordance with both ASTM E2632 and ASTM E2726 and
shall comply with the conditions of acceptance ...
Los Angeles Building Code > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 709A Decking
Section R337.9 Building Planning, Decking
The material shall
be tested in accordance with ASTM E2632 and shall comply
with the following condition of acceptance. The ASTM ...
R337.9.4.2 Building Planning, Conditions of Acceptance for ASTM E2726
The ASTM E2726 test shall be conducted on a
minimum of three test specimens and the conditions of
acceptance in Items 1 and 2 below shall be met. If ...
Los Angeles Residential Code > 3 Building Planning > R337.9 Decking > R337.9.4 Requirements for Type of Ignition-Resistant Material in Section R337.9.3, Item 1 > R337.9.4.2 Conditions of Acceptance for ASTM E2726