610.7 Conditions for Using Table 610.4
JUMP TO FULL CODE CHAPTER
On a proposed
water piping installation sized using Table 610.4, the following
conditions shall be determined:
- Total number of fixture units as determined from Table 610.3, Equivalent Fixture Units, for the fixtures to be installed.
- Developed length of supply pipe from meter to most remote outlet.
- Difference in elevation between the meter or other source of supply and the highest fixture or outlet.
- Pressure in the street main or other source of supply at the locality where the installation is to be made.
- In localities where there is a fluctuation of pressure in the main throughout the day, the water piping system shall be designed on the basis of the minimum pressure available.
Related Code Sections
610.7 Water Supply and Distribution, Conditions for Using Table 610.4
On a proposed
water piping installation sized using Table 610.4, the following
conditions shall be determined:
Total number of fixture units ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 610.0 Size of Potable Water Piping > 610.7 Conditions for Using Table 610.4
610.7 Water Supply and Distribution, Conditions for Using Table 610.4
On a proposed
water piping installation sized using Table 610.4, the following
conditions shall be determined:
Total number of fixture units ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 610.0 Size of Potable Water Piping > 610.7 Conditions for Using Table 610.4
610.4 Building Services and Systems, Cooking Oil Storage System Components
and other related components used for the transfer of cooking oil, and are permitted to be of either metallic or non-metallic construction ...
California Fire Code 2016 > 6 Building Services and Systems > 610 Commercial Kitchen Cooking Oil Storage > 610.4 Cooking Oil Storage System Components
11B-610.4 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Structural Strength
Allowable stresses shall not be exceeded for materials used when a vertical or horizontal force of 250 pounds (1112 N) is applied at any point ...
California Building Code 2016 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-610 Seats > 11B-610.4 Structural Strength
610.8 Water Supply and Distribution, Size of Meter and Building Supply Pipe Using Table 610.4
within which this pressure
will fall using Table 610.4.
Select the "length'' column that is equal to or longer than
the required length.
Follow ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 610.0 Size of Potable Water Piping > 610.8 Size of Meter and Building Supply Pipe Using Table 610.4