F307.1.2 Condensate Drains, Piping and Wiring Chases
JUMP TO FULL CODE CHAPTER
Condensate drain pipe joints shall be sealed (chemical weld, soldered, etc.) gas tight and shall terminate outside the building perimeter at a height of at least 6 inches (152 mm) above the finished grade ground level. Chases through which the condensate and refrigerant lines run shall not terminate in the return sections of the air distribution system. Where chase lines terminate within the house or garage, they shall be sealed.
Related Code Sections
B307.1.2 Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction, Condensate Drains, Piping and Wiring Chases
Condensate drain pipe joints shall be sealed (chemical weld, soldered, etc.) gas tight and shall terminate outside the building perimeter at a height ...
2020 FBC - Building, 7th edition > B Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction > B301 Construction Requirements for Passive Radon Control > B307 Space Conditioning Systems > B307.1 Equipment Enclosures > B307.1.2 Condensate Drains, Piping and Wiring Chases
F307.1.2 Florida Standard for Passive Radon-Resistant New Residential Building Construction, Condensate Drains, Piping and Wiring Chases
Condensate drain pipe joints shall be sealed (chemical weld, soldered, etc.) gas tight and shall terminate outside the building perimeter at a height ...
2017 FBC - Residential, 6th edition > F Florida Standard for Passive Radon-Resistant New Residential Building Construction > F307 Space Conditioning Systems > F307.1 Equipment Enclosures > F307.1.2 Condensate Drains, Piping and Wiring Chases
F307.1.2 Florida Standard for Passive Radon-Resistant New Residential Building Construction, Condensate Drains, Piping and Wiring Chases
Condensate drain pipe joints shall be sealed (chemical weld, soldered, etc.) gas tight and shall terminate outside the building perimeter at a height ...
2020 FBC - Residential, 7th edition > F Florida Standard for Passive Radon-Resistant New Residential Building Construction > F307 Space Conditioning Systems > F307.1 Equipment Enclosures > F307.1.2 Condensate Drains, Piping and Wiring Chases
C406.1.1 Florida Standard for Mitigation of Radon in Existing Buildings, Condensate Drains
Condensate drains shall connect to air outside the building perimeter at a height of at least 6 inches (172 mm) above the finished grade ground level ...
2017 FBC - Building, 6th edition > C Florida Standard for Mitigation of Radon in Existing Buildings > C406 Space Conditioning and Ventilation Systems > C406.1 Mechanical System Connections > C406.1.1 Condensate Drains
C406.1.1 Florida Standard for Mitigation of Radon in Existing Buildings, Condensate Drains
Condensate drains shall connect to air outside the building perimeter at a height of at least 6 inches (172 mm) above the finished grade ground level ...
2020 FBC - Building, 7th edition > C Florida Standard for Mitigation of Radon in Existing Buildings > C4 Structural Sealing and HVAC System Balancing > C406 Space Conditioning and Ventilation Systems > C406.1 Mechanical System Connections > C406.1.1 Condensate Drains