Reinforced and prestressed floors and roofs shall comply with Section 722.2.2.1. Multicourse floors and roofs shall comply with Sections 722.2.2.2 and 722.2.2.3, respectively.
722.2.2.1 Reinforced and Prestressed Floors and Roofs
The minimum thicknesses of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 722.2.2.1.
Exception: Minimum thickness shall not be required for floors and ramps within parking garages constructed in accordance with Sections 406.5 and 406.6.
MINIMUM SLAB THICKNESS (inches)
CONCRETE TYPE FIRE-RESISTANCE RATING (hours)
1 11/2 2 3 4
Siliceous 3.5 4.3 5 6.2 7
Carbonate 3.2 4 4.6 5.7 6.6
Sand-lightweight 2.7 3.3 3.8 4.6 5.4
Lightweight 2.5 3.1 3.6 4.4 5.1
For SI: 1 inch = 25.4 mm.
722.2.2.1.1 Hollow-Core Prestressed Slabs
For hollow-core prestressed concrete slabs in which the cores are of constant cross section throughout the length, the equivalent thickness shall be permitted to be obtained by dividing the net cross-sectional area of the slab including grout in the joints, by its width.
722.2.2.1.2 Slabs With Sloping Soffits
The thickness of slabs with sloping soffits (see Figure 722.2.2.1.2) shall be determined at a distance 2t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.

For SI: 1 inch = 25.4 mm.
FIGURE 722.2.2.1.2
DETERMINATION OF SLAB THICKNESS FOR SLOPING SOFFITS
722.2.2.1.3 Slabs With Ribbed Soffits
The thickness of slabs with ribbed or undulating soffits (see Figure 722.2.2.1.3) shall be determined by one of the following expressions, whichever is applicable:
For s > 4t, the thickness to be used shall be t
For s ≤ 2t, the thickness to be used shall be te
For 4t > s > 2t, the thickness to be used shall be

(Equation 7-5)
where:
s = Spacing of ribs or undulations.
t = Minimum thickness.
te = Equivalent thickness of the slab calculated as the net area of the slab divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t.


For SI: 1 inch = 25.4 mm.

FIGURE 722.2.2.1.3
SLABS WITH RIBBED OR UNDULATING SOFFITS
722.2.2.1.4 Flat Plate Concrete Slabs With Uniformly Spaced Hollow Voids
Table 722.2.2.1 shall be used to determine the 1- and 2-hour fire-resistance ratings for flat plate concrete slabs with uniformly spaced hollow voids. The equivalent thickness of the slab shall be determined by dividing the net concrete volume of the slab by the floor area. The net concrete volume of the slab shall be equal to the volume of concrete of a solid slab minus the average concrete volume displaced by the hollow voids.
722.2.2.2 Multicourse Floors
The fire-resistance ratings of floors that consist of a base slab of concrete with a topping (overlay) of a different type of concrete shall comply with Figure 722.2.2.2.

For SI: 1 inch = 25.4 mm.
FIGURE 722.2.2.2
FIRE-RESISTANCE RATINGS FOR TWO-COURSE CONCRETE FLOORS
722.2.2.3 Multicourse Roofs
The fire-resistance ratings of roofs that consist of a base slab of concrete with a topping (overlay) of an insulating concrete or with an insulating board and built-up roofing shall comply with Figures 722.2.2.3(1) and 722.2.2.3(2).

For SI: 1 inch = 25.4 mm.
FIGURE 722.2.2.3(1)

For SI: 1 inch = 25.4 mm.
FIGURE 722.2.2.3(2)
722.2.2.3.1 Heat Transfer
For the transfer of heat, three-ply built-up roofing contributes 10 minutes to the fire-resistance rating. The fire-resistance rating for concrete assemblies such as those shown in Figure 722.2.2.3(1) shall be increased by 10 minutes. This increase is not applicable to those shown in Figure 722.2.2.3(2).
722.2.2.4 Joints in Precast Slabs
Joints between adjacent precast concrete slabs need not be considered in calculating the slab thickness provided that a concrete topping not less than 1 inch (25 mm) thick is used. Where concrete topping is not used, joints must be grouted to a depth of not less than one-third the slab thickness at the joint, but not less than 1 inch (25 mm), or the joints must be made fire resistant by other approved methods.

Related Code Sections

722.2.2 Fire and Smoke Protection Features, Concrete Floor and Roof Slabs
thicknesses of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 722.2.2.1. Exception ...
722.2.2 Fire and Smoke Protection Features, Concrete Floor and Roof Slabs
of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 722.2.2.1. Exception ...
722.2.2.3 Fire and Smoke Protection Features, Multicourse Roofs
The fire-resistance ratings of roofs that consist of a base slab of concrete with a topping (overlay) of an insulating concrete or with an insulating ...
722.2.2.2 Fire and Smoke Protection Features, Multicourse Floors
The fire-resistance ratings of floors that consist of a base slab of concrete with a topping (overlay) of a different type of concrete shall comply ...
722.2.2.2 Fire and Smoke Protection Features, Multicourse Floors
The fire-resistance ratings of floors that consist of a base slab of concrete with a topping (overlay) of a different type of concrete shall comply ...