(3) Concrete-Encased Electrode
JUMP TO FULL CODE CHAPTER
A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either (1) or (2):
- One or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods of not less than 13 mm (1/2 in.) in diameter, installed in one continuous 6.0 m (20 ft) length, or if in multiple pieces connected together by the usual steel tie wires, exothermic welding, welding, or other effective means to create a 6.0 m (20 ft) or greater length; or
- Bare copper conductor not smaller than 4 AWG
Metallic components shall be encased by at least 50 mm (2 in.) of concrete and shall be located horizontally within that portion of a concrete foundation or footing that is in direct contact with the earth or within vertical foundations or structural components or members that are in direct contact with the earth. If multiple concrete-encased electrodes are present at a building or structure, it shall be permissible to bond only one into the grounding electrode system.
Informational Note: Concrete installed with insulation, vapor barriers, films or similar items separating the concrete from the earth is not considered to be in "direct contact" with the earth.
Related Code Sections
(3) Wiring and Protection, Concrete-Encased Electrode
A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either (1) or (2): One or more bare or zinc galvanized or other ...
National Electrical Code 2020 of Illinois > 2 Wiring and Protection > 250 Grounding and Bonding > 250.52 Grounding Electrodes > (A) Electrodes Permitted for Grounding > (3) Concrete-Encased Electrode
(3) Wiring and Protection, Concrete-Encased Electrode
A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either (1) or (2): One or more bare or zinc galvanized or other ...
National Electrical Code 2017 of Illinois > 2 Wiring and Protection > 250 Grounding and Bonding > 250.52 Grounding Electrodes > (A) Electrodes Permitted for Grounding > (3) Concrete-Encased Electrode
(C) Wiring and Protection, Grounding Electrode Conductor Connections
the structural steel column that are connected to a concrete-encased electrode complying with 250.52(A)(3) and located in the support footing or foundation ...
National Electrical Code 2020 of Illinois > 2 Wiring and Protection > 250 Grounding and Bonding > 250.68 Grounding Electrode Conductor and Bonding Jumper Connection to Grounding Electrodes > (C) Grounding Electrode Conductor Connections
250.50 Wiring and Protection, Grounding Electrode System
)(4) through (A)(8) shall be installed and used. Exception: Concrete-encased electrodes of existing buildings or structures shall not be required ...
National Electrical Code 2017 of Illinois > 2 Wiring and Protection > 250 Grounding and Bonding > 250.50 Grounding Electrode System
250.50 Wiring and Protection, Grounding Electrode System
)(4) through (A)(8) shall be installed and used. Exception: Concrete-encased electrodes of existing buildings or structures shall not be required ...
National Electrical Code 2020 of Illinois > 2 Wiring and Protection > 250 Grounding and Bonding > 250.50 Grounding Electrode System