1808.8.2 Concrete Cover
JUMP TO FULL CODE CHAPTER
The concrete cover provided for prestressed and nonprestressed reinforcement in foundations shall be not less than the largest applicable value specified in Table 1808.8.2. Longitudinal bars spaced less than 11/2 inches (38 mm) clear distance apart shall be considered to be bundled bars for which the concrete cover provided shall be not less than that required by Section 20.6.1.3.4 of ACI 318. Concrete cover shall be measured from the concrete surface to the outermost surface of the steel to which the cover requirement applies. Where concrete is placed in a temporary or permanent casing or a mandrel, the inside face of the casing or mandrel shall be considered to be the concrete surface.
FOUNDATION ELEMENT OR CONDITION | MINIMUM COVER |
1. Shallow foundations | In accordance with Section 20.6 of ACI 318 |
2. Precast nonprestressed deep foundation elements | |
Exposed to seawater | 3 inches |
Not manufactured under plant conditions
|
2 inches |
Manufactured under plant control conditions | In accordance with Section 20.6.1.3.3 of ACI 318 |
3. Precast prestressed deep foundation elements | |
Exposed to seawater | 2.5 inches |
Other | In accordance with Section 20.6.1.3.3 of ACI 318 |
4. Cast-in-place deep foundation elements not enclosed by a steel pipe, tube or permanent casing | 2.5 inches |
5. Cast-in-place deep foundation elements enclosed by a steel pipe, tube or permanent casing | 1 inch |
6. Structural steel core within a steel pipe, tube or permanent casing | 2 inches |
7. Cast-in-place drilled shafts enclosed by a stable rock socket | 1.5 inches |
For SI: 1 inch = 25.4 mm.
Related Code Sections
1808.8.2 Soils and Foundations, Concrete Cover
The concrete cover provided for prestressed and nonprestressed reinforcement in foundations shall be not less than the largest applicable value ...
Building Code 2018 of Illinois > 18 Soils and Foundations > 1808 Foundations > 1808.8 Concrete Foundations > 1808.8.2 Concrete Cover
1808.8.2 Soils and Foundations, Concrete Cover
The concrete cover provided for prestressed and nonprestressed reinforcement in foundations shall be not less than the largest applicable value ...
Building Code 2021 of Illinois > 18 Soils and Foundations > 1808 Foundations > 1808.8 Concrete Foundations > 1808.8.2 Concrete Cover
20.5.1 Steel Reinforcement Properties, Durability, & Embedments, Specified Concrete Cover
Unless the general building code requires a greater concrete cover for fire protection, the minimum specified concrete cover shall be in accordance ...
Building Code Requirements for Structural Concrete of Illinois > 20 Steel Reinforcement Properties, Durability, & Embedments > 20.5 Provisions for Durability of Steel Reinforcement > 20.5.1 Specified Concrete Cover
20.6.1 Steel Reinforcement Properties, Durability, and Embedments, Specified Concrete Cover
Unless the general building code requires a greater concrete cover for fire protection, the minimum specified concrete cover shall be in accordance ...
Building Code Requirements for Structural Concrete of Illinois > 20 Steel Reinforcement Properties, Durability, and Embedments > 20.6 Provisions for Durability of Steel Reinforcement > 20.6.1 Specified Concrete Cover
722.2.3.3.1 Fire and Smoke Protection Features, Calculating Concrete Cover
The concrete cover for an individual tendon is the minimum thickness of concrete between the surface of the tendon and the fire-exposed surface ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.3 Concrete Cover Over Reinforcement > 722.2.3.3 Prestressed Beam Cover > 722.2.3.3.1 Calculating Concrete Cover