Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

722.2.4 Concrete Columns

2015 Virginia Construction Code (USBC, Part I) > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.4 Concrete Columns
JUMP TO FULL CODE CHAPTER
Concrete columns shall comply with this section.
TABLE 722.2.4
MINIMUM DIMENSION OF CONCRETE COLUMNS (inches)
TYPES OF CONCRETE FIRE-RESISTANCE RATING
(hours)
1 11/2 2a 3a 4b
Siliceous 8 9 10 12 14
Carbonate 8 9 10 11 12
Sand-lightweight 8 81/2 9 101/2 12

For SI: 1 inch = 25 mm.
  1. The minimum dimension is permitted to be reduced to 8 inches for rectangular columns with two parallel sides not less than 36 inches in length.
  2. The minimum dimension is permitted to be reduced to 10 inches for rectangular columns with two parallel sides not less than 36 inches in length.

722.2.4.1 Minimum Size

The minimum overall dimensions of reinforced concrete columns for fire-resistance ratings of 1 hour to 4 hours for exposure to fire on all sides shall comply with this section.

722.2.4.1.1 Concrete Strength Less Than or Equal to 12,000 PSI

For columns made with concrete having a specified compressive strength, f 'c, of less than or equal to 12,000 psi (82.7 MPa), the minimum dimension shall comply with Table 722.2.4.

722.2.4.1.2 Concrete Strength Greater Than 12,000 PSI

For columns made with concrete having a specified compressive strength, f 'c, greater than 12,000 psi (82.7 MPa), for fire-resistance ratings of 1 hour to 4 hours the minimum dimension shall be 24 inches (610 mm).

722.2.4.2 Minimum Cover for R/C Columns

AMENDMENT
This section has been amended at the state or city level.
The minimum thickness of concrete cover to the main longitudinal reinforcement in columns, regardless of the type of aggregate used in the concrete and the specified compressive strength of concrete, f 'c, shall be not less than 1 inch (25 mm) times the number of hours of required fire-resistancefire resistance or 2 inches (51 mm), whichever is less.

722.2.4.3 Tie and Spiral Reinforcement

For concrete columns made with concrete having a specified compressive strength, f 'c, greater than 12,000 psi (82.7 MPa), tie and spiral reinforcement shall comply with the following:
  1. The free ends of rectangular ties shall terminate with a 135-degree (2.4 rad) standard tie hook.
  2. The free ends of circular ties shall terminate with a 90-degree (1.6 rad) standard tie hook.
  3. The free ends of spirals, including at lap splices, shall terminate with a 90-degree (1.6 rad) standard tie hook.
The hook extension at the free end of ties and spirals shall be the larger of six bar diameters and the extension required by Section 7.1.3 of ACI 318. Hooks shall project into the core of the column.

722.2.4.4 Columns Built Into Walls

The minimum dimensions of Table 722.2.4 do not apply to a reinforced concrete column that is built into a concrete or masonry wall provided all of the following are met:
  1. The fire-resistance rating for the wall is equal to or greater than the required rating of the column;
  2. The main longitudinal reinforcing in the column has cover not less than that required by Section 722.2.4.2; and
  3. Openings in the wall are protected in accordance with Table 716.5.
Where openings in the wall are not protected as required by Section 716.5, the minimum dimension of columns required to have a fire-resistance rating of 3 hours or less shall be 8 inches (203 mm), and 10 inches (254 mm) for columns required to have a fire-resistance rating of 4 hours, regardless of the type of aggregate used in the concrete.

722.2.4.5 Precast Cover Units for Steel Columns

See Section 722.5.1.4.

Related Code Sections


722.2.4 Fire and Smoke Protection Features, Concrete Columns
Concrete columns shall comply with this section. TABLE 722.2.4 MINIMUM DIMENSION OF CONCRETE COLUMNS (inches) TYPES OF CONCRETE ...
2015 Virginia Construction Code (USBC, Part I) > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.4 Concrete Columns
722.2.4 Fire and Smoke Protection Features, Concrete Columns
Concrete columns shall comply with this section. TABLE 722.2.4 MINIMUM DIMENSION OF CONCRETE COLUMNS (inches) TYPES OF CONCRETE FIRE ...
2012 Virginia Construction Code (USBC, Part I) > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.4 Concrete Columns
721.1.3 Fire and Smoke Protection Features, Reinforcement for Cast-In-Place Concrete Column Protection
Cast-in-place concrete protection for steel columns shall be reinforced at the edges of such members with wire ties of not less than 0.18 inch (4.6 ...
2015 Virginia Construction Code (USBC, Part I) > 7 Fire and Smoke Protection Features > 721 Prescriptive Fire-Resistance > 721.1 General > 721.1.3 Reinforcement for Cast-In-Place Concrete Column Protection
721.1.3 Fire and Smoke Protection Features, Reinforcement for Cast-In-Place Concrete Column Protection
Cast-in-place concrete protection for steel columns shall be reinforced at the edges of such members with wire ties of not less than 0.18 inch (4.6 ...
2012 Virginia Construction Code (USBC, Part I) > 7 Fire and Smoke Protection Features > 721 Prescriptive Fire Resistance > 721.1 General > 721.1.3 Reinforcement for Cast-In-Place Concrete Column Protection
Help Contact Us Privacy Terms
View thousands of relevant UL Certified products and assemblies that help achieve code compliance
View thousands of relevant UL Certified products and assemblies that help achieve code compliance
Access to UL product and system certification information.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
Join the waitlist
We are looking to gauge the level of interest in linking UL product and system certification information alongside related code sections.

Let us know your email and we’ll ping you once it’s ready! Learn more.

Thank you for your interest!

If you’re open to it, we would love to jump on the phone to make sure we’re building this in the best way possible for your workflow. Any insight or advice would be greatly appreciated. We’ve sent you an email with a calendar link to book at time with us.


Cancel
Get Early Access
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE